Burkert Type 8620 User Manual
Page 148

mxCONTROL Type 8620
Page 148
Warning or
Error message
Displayed as
Displaying
interval
Cause
Remedy
Max.Value
overflow
short message
once
The current set value is
greater than the maximum
value of this parameter.
The value is set to the
maximum value and can be
edited before confirmation.
Min.Value
underflow
short message
once
The current set value is lower
than the minimum value of
this parameter.
The value is set to the
minimum value and can be
edited before confirmation.
Edit the value, if required,
and then confirm the new
value by pressing ENTER.
If the old value should be
kept, press ESC.
MOT expired
permanent
message
once
At least one of the maximum
output timer has expired and
the corresponding outputs are
set to zero.
Search for the
corresponding module in
the Process data.
To enable the associated
outputs again, the MOT
alarm has to be
acknowledged in the
corresponding process data
menu of the associated
module.
No Permission
permanent
message
once
A file is downloaded without
the right authorization (current
code level restricts the
download of this file type).
The downloaded data is not
accepted.
If you are authorized, return
to the main menu under the
menu item
Upload/Download
, enter
the correct password this
time (CodeLevel: Specialist
/ Master) and start the
download again.
No SD-Card
detected
short message
during upload or
data logging:
permanent
message
once
once
No SD card detected.
Check, if the SD card is
inserted correctly into the
SD card slot.
Then return in the menu
structure to the according
menu item
- Upload or
- Download or
- Data Logging
and start the procedure
again.
SD can be
removed
short message
once
SD card has operated
successfully and can be
removed from the SD card
slot.
--