Configuration (code level: specialist) – Burkert Type 8620 User Manual
Page 76

mxCONTROL Type 8620
Page 76
→ Select
„Offset“,
press key “INPUT”
(Æ the device outputs now a current of 4 mA at the 4-20mA output X)
→ Measure the real current through the resistor R
→ Input the measured current value (via keys „+“ and „<-“),
press key "OK"
→ Select
„Span“,
press key “INPUT”
(Æ the device outputs now a current of 20 mA at the 4-20mA output X)
→ Measure the real current through the resistor R
→ Input the measured current value (via keys „+“ and „<-“),
press key "OK"
→ Select
“End”;
press key “ENTER”.
Leaving this menu item the analog output will be calibrated based on the
input values (Offset, Span) and will be re-initialized.
The user calibration data are stored in Eeprom when returning to the main
menu.
If „Factory Values“ is selected, the user calibration data will be
overwritten with the factory calibration values.
If „Factory Reset“ was activated, the user calibration data of all 4-20mA-
outputs are overwritten with factory calibration values.
Configuration (Code Level: Specialist)
Configuration
Access
via Cfg.-
menu
Access
via XML-
Cfg.-File
Abbre-
viation
(menu)
Value range
Default values
(after factory reset or
at start of Cfg-File-
Download)
Enabling / disabling
output
rw rw Output
On/Off
Off
Sense of action of the
current output
rw
rw
Dir
Rise / Fall
Rise