3 (remote) device access via pc-tool – Burkert Type 8620 User Manual
Page 52

mxCONTROL Type 8620
Page 52
Configuration
Access
via Cfg.-
menu
Access
via XML-
Cfg.-File
Abbrevia-
tion
(menu)
Value range
Default values
(after factory reset or
at start of Cfg-File-
Download)
Notification
Notification via email
rw
rw
Via email
Yes, No
No
SMTP mail server (#) (***)
IP address of mail server
rw
rw
IP
0.0.0.0 …
255.255.255.255
0.0.0.0
Port number for SMTP
rw
rw
Port
0 … 65535
25
Email (***)
Device´s sender address
(#)
rw rw From
(sender)
max. 47 characters
(***** *)
[[email protected]]
Recipient 1
rw
rw
To (reci-
pient 1)
max. 39 characters
[[email protected]]
Recipient 2
rw
rw
To (reci-
pient 2)
max. 39 characters
[[email protected]]
Email 1, Email 2, Email 3 (***)
Email Trigger
rw
rw
Trigger
On, Off
On
Email priority (for display in
email program on PC)
rw
rw
Priority
1 (highest) …
5 (lowest)
1
Renotification interval (****) rw
rw
ReNotify
0 (off) … 10800 min
0 min
Email subject
rw
rw
Subject
max. 23 characters
[a-zA-Z0-9 _.:/!+*-]
Email
1: Alarm
2: Warning/Error
3: Device Restarted
(#)
Ask your local network administrator for the right settings.
(*)
Only visible, if Static IP = Yes
(**)
Only visible, if Static IP = No
(***)
Only visible, if Via email = Yes
(****)
Only available for email 1 and email 2
(*****) ID = Device ident no. (8 digits with ledig zeros),
SERIAL = Device serial no. (7 digits with ledig zeros)
(***** *) Empty string activates default sender address: 8620_ID_SERIAL with (*****)
11.5.3 (Remote) Device access via PC-Tool
Remote device access allows operating the controller via Ethernet (devices with Ethernet option only)
or via USB.
Remote device access can be disabled only directly at the device – in the configuration menu:
USB:
Configuration \ Communication \ USB \ PCToolAccess
On (default) / Off
Ethernet:
Configuration \ Communication \ Ethernet \ PCToolAccess
On (default) / Off
Configuration of PCToolAccess is not stored in the configuration file.
The PCToolAccess has to be disabled manually again in case of factory reset.
The device can handle only one remote device access at one time.