beautypg.com

5 configuration (code level: specialist) – Burkert Type 8620 User Manual

Page 79

background image

mxCONTROL Type 8620


Page 79

13.3.5 Configuration (Code Level: Specialist)

Configuration

Access
via Cfg.-
menu

Access
via XML-
Cfg.-File

Abbre-
viation
(menu)

Range

Default values

(after factory reset or
at start of Cfg-File-
Download)

Enabling / disabling
output

rw rw Output

On/Off

Off

Transistor Output Type rw

rw

Type

On/Off, PFM, PWM, fast
PWM

enable/disable

Inversion of the output
signal

rw

rw

Inv

Yes / No

No

Additional configuration, if Transistor Output Type = PFM selected
Unit pulse duration

rw

rw

Tpuls Unit

s, ms

ms

Pulse duration

rw

rw

Tpuls

1 … 9999

100 ms

Unit
Max. pulse frequency

rw

rw

Fmax Unit

/min, /h

/min

Max pulses per time

rw

rw

Fmax

1 … MAX
MAX <= 9999 and MAX
depend on the current
unit and pulse duration:
MAX = 1/Tpuls with
Tpuls in units of 1/(unit of
Fmax)

160/min

Additional configuration, if Transistor Output Type = PWM selected
Unit of period duration

rw

rw

Tperiod
Unit

s, ms

s

period duration

rw

rw

Tperiod

1 … 9999 s or
100 … 9999 ms

10 s

Additional configuration, if Transistor Output Type = fast PWM selected
PWM frequency

rw

rw

Freq

20 … 2250 Hz

30.1Hz

Limitiation of the manipulating speed,
if transistor output type "Fast-PWM" or "PWM" was selected
Opening time for entire
manipulated variable
range 0% -> 100%

rw

rw

Topen

0.0 ... 60.0 s

10.0 s

Closing time for entire
manipulated variable
range 100% -> 0%

rw

rw

Tclose

0.0 ... 60.0 s

10.0 s