Burkert Type 8620 User Manual
Page 152
mxCONTROL Type 8620
Page 152
Warning or
Error message
Displayed as
Displaying
interval
Cause
Remedy
User Calib
failed
permanent
message
once
User calibration of 4-20mA
Output failed. Old user
calibration values kept.
Check the wiring and make
sure that you connected
load and the ampmeter
correctly.
Try again.
Refer also to Description of
User Calibration in Chapter
13.2 “Calibration of 4 ... 20
mA Outputs”.
Wrong
ParamFile!
short message
once
The currently downloaded
Parameter-File does not suit
the current configuration.
The old parameters are
restored after the download
has finished or has been
cancelled.
Download the right
parameter file.
Usually the Parameter file
has a similar file name like
the configuration file, but
begins with “Par” or
“Param” instead of “Cfg”.
The controller carries out a self test each time power is restored, including checking current date,
calibration data and EEPROM data.
The analog inputs are checked periodically during the input-sampling process.