Burkert Type 8620 User Manual
Page 144

mxCONTROL Type 8620
Page 144
15.2
Displaying (Input-) Alarms and different
(Output-) States
The input alarms and output states are displayed in the "Process data" main menu in the "Input" submenu items
and in the submenus of the corresponding modules.
Display
Input State
AL
Lower Alarm
FS
Sensor Fault
AH
Higher Alarm
FA
AD-Fault
WL
Lower Warning
FC
Configuration Fault
WH
Higher Warning
Fc
Calibration Data Fault
FI
Input Fault
nA
Input not active
OK
Output status or output is calculated/impacted by:
Au
Automatic Mode
fo
an other module
Ma
Manual Mode
fF
(active) Flow-Switch
OF
4…20 mA Output error
fS
(active) System
YA
ASL-Pump-Stop
Switch
YS
Safety control output (CMDsafe) Fc
Calibration Data Fault
is active
(only in menu “Out-
YF
Out fails (MOT is expired)
puts” for 4-20 mA
outputs)
Additionally the following icons are displayed in parent menus for easy alarm / warning identification:
Icon
Priority
Description
A!
1 (High)
There is at least one alarm in the submenus.
W
2
There is at least one warning in the submenus
!
3
There is at least one configuration error in the submenus
4 (Low)
OK
Only the item with the highest priority is displayed, if there is a mixture of alarms / warnings / configuration errors
in the submenus.