Processdata and Data Logging
Display-Presentation
Displayed data
Abbre-
viation
(menu)
Full
Screen
Trend
chart
Line
Data-
Log.
Notes
Process value
PV
x x x
x
Set point
SP
x x
x
Set point vs. Process value
SP/PV
x
Module output
CMD
x x
x
Alarm Maximum Output Timer
x
x
displayed only, if
MOT enabled and
expired;
Data log in Module
output
Parameter (Code Level: Operator)
Parameter
Abbrevia-
tion
(menu)
Value range
Default values
(after successful download of
Cfg-File)
Sample Time
Tsample
0.05/0.1 … 60.0 s
0.2 s
Set point
SP
Scal- …Scal+ of the assigned input
Scal- + ((Scal+ - Scal-) /2)
Gain/amplification factor
Kp
0.001 … 9999.0 (in % / unit)
10.0
Reset time
Tn
0.1 … 9999.0 s
9999.0 s
Lower output limit
Lim-
0.0 … Lim+
0.0 %
Upper output limit
Lim+
Lim- … 100.0 %
100.0 %
Safety output value
CMDsafe
0.0 … 100.0 %
0.0%
Maximum output timer (MOT)
Maximum output time (*)
+Tm
1 ... 10800 s
10800 s
(*) will be only displayed if the parameter “MOT” is configured as “Yes” in the menu „Configuration“
Configuration (Code Level: Specialist)
Configuration
Access
via
Cfg.-
menu
Access
via XML-
Cfg.-File
Abbreviation
(menu)
Value range
Default values
(after factory reset or
at start of Cfg-File-
Download)
Module active/not active rw
rw
Module
On/Off
Off
Inversion module sense
of action
rw
rw
InvMod
Yes / No
No
System switch override
rw
rw
SSOR
Yes / No
No
Flow switch override
rw
rw
FSOR
Yes / No
No
Maximum Output Timer
rw
rw
MOT
Yes / No
No