Ac input wire – Xantrex Technology XDC 20-600 User Manual
Page 46
![background image](/manuals/229298/46/background.png)
Installation
2–8
TM-XDOP-01XN
AC Input Wire
The manufacturer recommends the AC input wire specified in Table 2-2 and Table
2-3. This must be permanently connected to an approved AC distribution box with
suitably rated over-current protection. If you require a special cord, contact the
manufacturer.
f
Table 2-2 AC Wire Specification for 6000 Watt Units
AC Input Voltage Range
Wire
190–242Vac, 47–63Hz,
3-phase, 4 wire (standard)
4 x 10 AWG (3 wire plus safety ground), stranded
copper, 60
°
C minimum, 300V, 0.800 in.
maximum cable diameter, rated for 25A.
342–500Vac, 47–63Hz,
3-phase, 4 wire (HV-Input)
4 x 14 AWG (3 wire plus safety ground), stranded
copper, 60
°
C minimum, 600V, 0.800 in.
maximum cable diameter, rated for 13A.
Table 2-3 AC Wire Specification for 12000 Watt Units
AC Input Voltage Range
Wire
190–242Vac, 47–63Hz,
3-phase, 4 wire (standard)
4 x 6 AWG (3 wire plus safety ground), stranded
copper, 60
°
C minimum, 300V, outside diameter
(OD) of cable is
≤ 1 in., rated for 50 A.
342–500Vac, 47–63Hz,
3-phase, 4 wire (HV-Input)
4 x 10 AWG (3 wire plus safety ground), stranded
copper, 60
°
C minimum, 600V, outside diameter
(OD) of cable is
≤ 1 in., rated for 25 A.
TM-XDOP-01XN.book Page 8 Monday, July 17, 2006 11:19 AM