beautypg.com

Xantrex Technology XDC 20-600 User Manual

Page 200

background image

Specifications and Characteristics

A–8

TM-XDOP-01XN

Typical Programming Resolution

Typical Measurement Resolution

Programming Accuracy

1

Readback Accuracy

Front Panel or Remote Digital Interface

Voltage
Current
Power
Over Voltage Protection

0.002% of Vmax
0.002% of Imax
0.05% of Pmax
0.002% of Vmax

Remote Analog Programming Interface

Voltage
Current

0.002% of Vmax
0.002% of Imax

Front Panel or Remote Digital Interface

Voltage
Current
Power

0.002% of Vmax
0.002% of Imax
0.05% of Pmax

Remote Analog Programming Interface

Voltage
Current

0.002% of Vmax
0.002% of Imax

1.

Accuracy specifications apply for settings in range of 1% to 100% of rated output

Front Panel or Remote Digital Interface

Voltage Programming
Current Programming
Power Programming
Over voltage
Programming

0.1% of Vmax
0.5% of Imax
0.5% of Pmax
0.1% of Vmax

Remote Analog Programming Interface

Voltage Programming
Current Programming

0.2% of Vmax
0.5% of Imax

Front Panel or Remote Digital Interface

Voltage Readback
Current Readback
Power Readback

0.15% of Vmax
0.5% of Imax
0.5% of Pmax

Remote Analog Programming Interface

Voltage Readback
Current Readback

0.3% of Vmax
0.5% of Imax

TM-XDOP-01XN.book Page 8 Monday, July 17, 2006 11:19 AM