beautypg.com

Xantrex Technology XDC 20-600 User Manual

Page 242

background image

SC
PI Co

mmand Re

fe

ren
ce

C–18

TM-XDOP-01XN

Table C-7 Commands for Fold Protection

Function

SCPI Command

Description

Query

Set Output Fold
Delay

[:]OUTPut[]:PROTection:FOLD:DELay

Set the delay time (seconds)
before fold protection is triggered.

Yes

Set Output Fold
Mode

[:]OUTPut[]:PROTection:FOLD[:MODE]

{NONE|CC|CP|CV}

Select which regulation mode to
fold back (None, CV, CC, CP)

Yes

Query Fold
Protection Tripped

[:]OUTPut[]:PROTection:FOLD:TRIPped?

Query if fold protection has
tripped

N/A

Table C-8 Commands for Triggering

Function

SCPI Command

Description

Query

Set Immediate
Initiation of Trigger
System

[:]INITiate[][:IMMediate]

Initiate a triggered event or
sequence

N/A

Set Trigger Source

[:]TRIGger[][:SEQuence]:SOURce

{BUS|EXTernal|IMMediate|NONE}

Sets the trigger source for
triggered setpoints

Yes

TM-XDOP-01XN.book Page 18 Monday, July 17, 2006 11:19 AM