Table 4-4), Table 4-4 – AMETEK ASD Series User Manual
Page 71
Sorensen ASD Series
Programming: Digital Interface Control
M551177-01 Rev A
4-13
Table 4-4. Write Registers
Address
Name
IQ
Content
Notes
0
Command
binary
See Command description below.
1, 2
Vsetpoint_HI/LO
IQ15 / FP
Output voltage setpoint. 1.0 = nominal voltage (60V / 40V).
2, 3
3, 4
Isetpoint_HI/LO
IQ15 / FP
Output current setpoint. 1.0 = nominal current of one module (167A / 250A).
2, 3
5, 6
Psetpoint_HI/LO
IQ15 / FP
Output power (or process) setpoint. 1.0 = nominal power of one module (10020W / 10000W).
2, 3
7, 8
Module_Vout_peak_HI/LO
IQ15 / FP
Overvoltage protection threshold. 1.0 = nominal voltage (60V / 40V).
2. 3
9, 10
Zoutput_ Max_HI/LO
IQ24 / FP
Output impedance max limit. 1.0 = (nominal voltage / nominal current) of one module (0.3593
/ 0.1600
).
2, 3
11, 12
Zoutput_ Min_HI/LO
IQ24/ FP
Output impedance min limit. 1.0 = (nominal voltage / nominal current) of one module (0.3593
/ 0.1600
).
2, 3
13, 14
Zoutput_ ROC_Pos_HI/LO
IQ20 / FP
Output impedance rate-of-chance max limit. Percent of change per second.
2, 3
15, 16
Zoutput_ ROC_Neg_HI/LO
IQ20 / FP
Output impedance rate-of-chance min limit. Percent of change per second.
2, 3
17, 18
Fault_Shutdown_Config_HI/LO
binary
All bits that are “1” will cause the corresponding fault bit to generate a shutdown the unit.
3, 4
19, 20
Zcable_Max_HI/LO
IQ24 / FP
Cable impedance max limit. 1.0 = (nominal voltage / nominal current) of one module (0.3593
/ 0.1600
).
2, 3
21, 22
Vdrop_Cable_Max_HI/LO
IQ15 / FP
Cable voltage drop max limit. 1.0 = nominal voltage (60V / 40V).
2, 3
23, 24
Zmonitor_Imin_HI/LO
IQ15 / FP
Impedance monitor minimum required current. 1.0 = (nominal voltage / nominal current) of one module
(0.3593
/ 0.1600
).
3
25, 26
Zalpha_HI/LO
IQ24 / FP
Alpha coefficient of the low pass filter for all impedance calculations. Normalized (0 to 0.9999).
3
27
Save_Defaults
binary
0x1234 stores current state as default, 0x5678 restores saved default, 0x9ABC restores factory defaults.
28
Query_Module
binary
Used to query module data, in combination with Read registers 29, 30 (Query_Module_Info).
29
Expected_Modules
Int16
If non-zero a fault will be generated when existing modules does not match this value. See user guide for
more details.
30
FDR_Period
Int16
See FDR_Period description below for more information.
31, 32
Vsetpoint_SRL_HI/LO
IQ15 / FP
Voltage setpoint slew-rate-limit. 1.0 = nominal voltage (60V / 40V) per ms voltage setpoint rate-of-change
limit.
2, 3
33, 34
Isetpoint_SRL_HI/LO
IQ15 / FP
Current setpoint slew-rate-limit. 1.0 = nominal current of one module (167A / 250A) per ms current setpoint
rate-of-change limit.
2, 3
35, 36
monitor_alpha_HI/LO
IQ24 / FP
Alpha coefficient of the low pass filter for the monitor readbacks. Normalized (0 to 0.9999).
2, 3
37, 37
max_delta_setpoint_HI/LO
IQ15 / FP
Used for impedance calculation. If setpoints change more than this value the impedance measurement is
considered not valid. Percent per ms.
2, 3
39
Z_delay
Int16
Used for impedance calculation. Time delay after the impedance calculation is considered valid again. 1 is
equivalent to 8 ms of delay
40
Modbus_timeout_period
Int16
Used with Modbus timeout feature. 1 is equivalent to 8 ms of delay
41, 42
activation_code_HI/LO
Int32
Code to unlock the digital interface. A value of all ones (
4294967295) will lock it. The correct unlock code
is based on an encryption algorithm and the Master Controller serial number.
3