Sorensen ASD Series

Installation

M551177-01 Rev A

2-33

2.6

WIRE SELECTION

Care must be taken to properly size all conductors for the input and output
of the power supply. This section provides guidance in the selection of
wire size. Note that cables with Class B or C stranding should be used.
Fine stranded cables should not be used unless crimp-on lugs or ferrules
are used that are approved for fine stranded cables.

2.6.1 WIRE SIZE

The tables below will assist in determining the appropriate wire size for
both the input and output connections Table 2-7 below gives minimum
recommended wire size. This table is derived from the National Electrical
Code; it is for reference only. Local laws and conditions may have
different requirements. Note that these recommendations are for copper
wire only. For higher ratings, wires can be paralleled; refer to the National
Electrical Code.

Table 2-7. Minimum Wire Size

Size

Temperature Rating of Copper Conductor

AWG
MCM

60°C

75°C

85°C

90°C

Types: RUW,

T, TW, UF

Types: FEPW,

RHW, RH, RUH,

THW, THWN,

XHHW, USE, ZW

Types: V, MI

Types: TA, TBS,

SA, AVB, SIS, FEP,

FEPB, RHH, THHN,

XHHW

Current Rating

14

20

20

25

25

12

25

25

30

30

10

30

35

40

40

8

40

50

55

55

6

55

65

70

75

4

70

85

95

95

3

85

100

110

110

2

95

115

125

130

1

110

130

145

150

0

125

150

165

170

00

145

175

190

195

000

165

200

215

225

0000

195

230

250

260