2-33
2.6
WIRE SELECTION
Care must be taken to properly size all conductors for the input and output
of the power supply. This section provides guidance in the selection of
wire size. Note that cables with Class B or C stranding should be used.
Fine stranded cables should not be used unless crimp-on lugs or ferrules
are used that are approved for fine stranded cables.
2.6.1 WIRE SIZE
The tables below will assist in determining the appropriate wire size for
both the input and output connections Table 2-7 below gives minimum
recommended wire size. This table is derived from the National Electrical
Code; it is for reference only. Local laws and conditions may have
different requirements. Note that these recommendations are for copper
wire only. For higher ratings, wires can be paralleled; refer to the National
Electrical Code.
Table 2-7. Minimum Wire Size
Size
Temperature Rating of Copper Conductor
AWG
MCM
60°C
75°C
85°C
90°C
Types: RUW,
T, TW, UF
Types: FEPW,
RHW, RH, RUH,
THW, THWN,
XHHW, USE, ZW
Types: V, MI
Types: TA, TBS,
SA, AVB, SIS, FEP,
FEPB, RHH, THHN,
XHHW
Current Rating
14
20
20
25
25
12
25
25
30
30
10
30
35
40
40
8
40
50
55
55
6
55
65
70
75
4
70
85
95
95
3
85
100
110
110
2
95
115
125
130
1
110
130
145
150
0
125
150
165
170
00
145
175
190
195
000
165
200
215
225
0000
195
230
250
260