Specifications – AMETEK ASD Series User Manual

Page 20

background image

Overview

Sorensen ASD Series

1-22

M551177-01 Rev A

1.2

SPECIFICATIONS

The following subsections provide environmental, electrical, and physical
characteristics for the ASD Series power supplies.

Note: Specifications are subject to change without notice.

Note: The ASD Series power supplies are intended for indoor use only. Please refer
to Section 2.3 for use/location requirements.

1.2.1 ENVIRONMENTAL CHARACTERISTICS

Parameter

Specification

Temperature
Coefficient

0.02%/

C of maximum output voltage rating for voltage set point.

0.03%/

C of maximum output current rating for current set point.

Ambient Temperature

Operating

0 to 50

C

Storage

-25

to 65

C

Cooling, by water

Flow (gpm)

1.5 nominal, 1.25 minimum, 1.75 maximum
NOTE:
Internal condensation must be prevented by ensuring
that the coolant is sufficiently high compared with the
ambient air dew point.

Temperature

25

C nominal, 20

C minimum, 30

C maximum

Pressure

80 PSI maximum

Pressure drop

Typical 12 PSI @ 1.5gpm per chassis

Humidity

Relative humidity up to 95% maximum, non-condensing

Altitude

Operating full power available up to 5,000 feet (1,524m),
derate 10% of full power for every 1,000 feet higher
non-operating to 40,000 feet (12,192m)

Agency Approvals

NRTL certified to UL/CSA 61010 and IEC/EN 61010-1, CE Compliant,
LVD Categories: Installation Category II: Pollution Degree 2; Class II
Equipment: for Indoor Use Only. Rack mount equipment requires proper
enclosure provided in end use. EMC Directive, EN 661326:1998