Programming: Digital Interface Control

Sorensen ASD Series

4-52

M551177-01 Rev A

Current Programming
Disable

Disables the analog current programming signal
and sets the current setpoint to either the full-scale
current or the digital current setpoint - depending on
the Disable Analog Saturate setting (below).

Power Programming
Disable

Disables the analog power programming signal and
sets the power setpoint to either the full-scale power
or the digital power setpoint - depending on Disable
Analog Saturate setting (below).

Digital Programming Mode

Black/True sets the power supply into digital
programming mode so the power supply must be
turned on and off through digital programming and
uses the digital setpoints for current, voltage and
power. White/false the power supply is in analog
programming mode and the power supply must be
turned on and off through the analog interface and
uses the analog setpoints for current, voltage and
power

Disable Analog Saturation

if any of the analog programming signals are
disabled, their setpoint will be taken from the digital
programming setpoint; if this button is false, then
any disabled analog programming

signal’s setpoint

will be set to the full-scale value

.