C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 82

Important parameters:
MCPS: Installer menu

General parameters

Aux1 Circuit

MCPS: Installer Menu

General parameters

pumps alarm CFG

AUX1 pump

MCPS: Maintenance Menu

Aux1 Management

Setpoint

MCPS: Maintenance Menu

Aux1 Management

Hysteresis

MCPS: Maintenance Menu

Aux1 Management

Probe offset

MCPS: Maintenance Menu

Aux1 Management

Mode


9.5.5

Control of the high and low temperature of the auxiliary circuit AUX1
(MCPS module)

Whenever the temperature of the AUX1 auxiliary circuit water exceeds or drops below the
minimum and maximum temperature values accepted for the system of the hysteresis value, then
the c-pro micro MCPS solar panels regulator will start special management cycles for these
emergencies:

-

High temperature protection: the high temperature protection intervention will trigger a
simple signal to the maintenance staff.

-

Low temperature protection: the low temperature protection will trigger the activation of the
circulation pump of the auxiliary circuit in order to ease heating of the circuit water. The
pump will remain on until the minimum temperature conditions are recovered.


Important parameters:
MCPS: Maintenance Menu

Aux1 Management

HT setpoint

MCPS: Maintenance Menu

Aux1 Management

HT hyst.

MCPS: Maintenance Menu

Aux1 Management

LT setpoint

MCPS: Maintenance Menu

Aux1 Management

LT hyst.


9.5.6

Management and setting of the periodic antilegionella cycle for the DHW
tank (MCPS module)

In order to disinfect the DHW tank from the proliferation of legionella bacteria due to the deposit of
DHW, the c-pro CLIMA system envisions the periodic management of anti-legionella cycles.
Depending on the type of system, it is possible to select daily, weekly or monthly antilegionella
cycles.
An anti-legionella cycle consists in taking, the temperature of the DHW tank to a temperature such
to destroy bacteria (standard to 70°C, but which can be set from parameter) for a long enough
period of time (standard at 60 minutes, but can be set from parameter) by activation of the boiler
and the DHW circulation pump.
These periodic cycles will help with respect to the Standards in force on the subject.

Important parameters:
MCPS: Maintenance Menu

General parameters

Antilegionella

Enable

MCPS: Maintenance Menu

General parameters

Antilegionella

Mode

MCPS: Maintenance Menu

General parameters

Antilegionella

Start hour

MCPS: Maintenance Menu

General parameters

Antilegionella

Day week

MCPS: Maintenance Menu

General parameters

Antilegionella

Day month

MCPS: Maintenance Menu

General parameters

Antilegionella

Setpoint

MCPS: Maintenance Menu

General parameters

Antilegionella

Duration