9.3.3

Zone humidity work set-point (MCZN module)

The zone humidity work set-point is decided in manual mode via the relative maintenance technical
parameters present in the c-pro micro MCZN zone regulator or automatically, set by the final user
via programmed weekly time bands.
To set the automatic humidity work set-points (Economy and Comfort set-points), consult the c-pro
CLIMA system user manual.

Important parameters:
MCZN: Maintenance Menu

Zone A(B) Maintenance

Humid. regulation

COMFORT

MCZN: Maintenance Menu

Zone A(B) Maintenance

H. Regulation

ECONOMY


9.3.4

Management and configuration of the c-pro micro MCDE module for
additional dehumidifiers (MCZN, MCDE modules)

As well as direct control of the manifold/zone dehumidification valve, the c-pro CLIMA system has
the possibility of managing various types of additional dehumidifiers via CANbus, equipped with
utilities (fans/batteries) dedicated to increasing heating/cooling capacities of the controlled system.
To use these types of additional dehumidifiers, the c-pro micro MCDE module must be used.
As previously described, the additional dehumidifiers can be associated to a zone regulator and can
serve just one of the controlled areas (Zone A or Zone B) or both, depending on the type and size of
the controlled rooms.

Depending on the type of dehumidifier used in the system, via the relevant parameter, the c-pro
micro MCDE module assumes a different functioning type, varying the type of utility managed by
the digital outputs, as follows:

Digital outputs configuration
Dehumidif. type 0: DO1 = zone A dehumidifier DO4 = not used
DO2 = not used DO5 = zone A dehumidif. alarm
DO3 = zone B dehumidifier DO6 = zone B dehumidif. alarm

Dehumidif. type 1: DO1 = dehumidifier DO4 = fresh air damper
DO2 = heating booster DO5 = dehumidifier alarm
DO3 = cooling booster DO6 = not used

Dehumidif. type 2: DO1 = zone A dehumidifier DO4 = heat./cool. booster zone B
DO2 = heat./cool. booster zone A DO5 = zone A dehumidif. alarm
DO3 = zone B dehumidifier DO6 = zone B dehumidif. alarm

Important parameters:
MCZN: Installer Menu

Dehumidifier

Rem. dehumidifier

Enab. control

MCZN: Installer Menu

Dehumidifier

Rem. dehumidifier

CANBUS address


MCDE: Installer menu

General parameters

MCZN assigned

MCDE: Installer menu

General parameters

CANBUS address

MCDE: Installer Menu

Dehumidifyer

Dehum. type

MCDE: Maintenance Menu

General parameters

Regulations

Dehumidifyer

MCDE: Maintenance Menu

General parameters

Regulations

Dehum. delay