Important parameters:
MCZN: Installer menu

General parameters

Local zones nr.

MCZN: Installer menu

Zones

Zona A(B)

Delivery line

MCZN: Installer menu

Zones

Zone A(B)

Terminal units

MCZN: Installer menu

Zones

Zone A(B)

Sensor type

MCZN: Installer menu

Zones

Zone A(B)

T. probe pos.

MCZN: Installer menu

Zones

Zone A(B)

Reg. type

MCZN: Maintenance Menu

Zone A(B) Maintenance

Regulation enablings

Temperature

MCZN: Maintenance Menu

Zone A(B) Maintenance

Temp. regulation

Hysteresis


9.1.3

Zone work set-point (MCZN module)


The zone work set-point is decided depending on the work mode, manual or automatic (with
programmed weekly time bands), always using the Vgraph zone display.
For the types of work set-point acceptable and for their settings, consult the c-pro CLIMA system
user manual.
Other possibilities also exist to change the work set-point established via Vgraph in the modes listed
below:

9.1.3.1

Variation of the zone work set-point for "climatic curves" (MCZN, MCCT
modules)

By activating the work set-point variation function for “climatic curve”, depending on the external
temperature it is possible (available on the MCCT regulator) to vary the active zone work set-point
value within the minimum and maximum limits that can be set from parameter, in order to adapt the
room temperature to the external climatic conditions, as follows:

-

set the minimum and maximum external temperature limits specific for summer functioning
and winter functioning, within which the variation function of the room set-point is active

-

the room work set-point minimum and maximum variation values are set

-

set the direction of the compensation if direct or inverse for increase or decrease
compensation of the work set-point.


Important parameters:
MCZN: Maintenance Menu

Zone A(B) Maintenance

Regulation enabling

T. Ext set var.

MCZN: Maintenance Menu

Zone A(B) Maintenance

T.ext set variation

MinTExt S

MCZN: Maintenance Menu

Zone A(B) Maintenance

T.ext set variation

MaxTExt S

MCZN: Maintenance Menu

Zone A(B) Maintenance

T.ext set variation

MinTExt Set S

MCZN: Maintenance Menu

Zone A(B) Maintenance

T.ext set variation

MaxTExt Set S

MCZN: Maintenance Menu

Zone A(B) Maintenance

T.ext set variation

ModeTExt Set S

MCZN: Maintenance Menu

Zone A(B) Maintenance

T.ext set variation

MinTExt W

MCZN: Maintenance Menu

Zone A(B) Maintenance

T.ext set variation

MaxTExt W

MCZN: Maintenance Menu

Zone A(B) Maintenance

T.ext set variation

MinTExt Set W

MCZN: Maintenance Menu

Zone A(B) Maintenance

T.ext set variation

MaxTExt Set W

MCZN: Maintenance Menu

Zone A(B) Maintenance

T.ext set variation

ModeTExt Set W