EVCO c-pro CLIMA sistema Installer manual User Manual
Page 69
C-PRO CLIMA SISTEMA INSTALLER MANUAL
Page 69
Important parameters:
MCZN: Installer menu
General parameters
Local zones nr.
MCZN: Installer menu
Zones
Zona A(B)
Delivery line
MCZN: Installer menu
Zones
Zone A(B)
Terminal units
MCZN: Installer menu
Zones
Zone A(B)
Sensor type
MCZN: Installer menu
Zones
Zone A(B)
T. probe pos.
MCZN: Installer menu
Zones
Zone A(B)
Reg. type
MCZN: Maintenance Menu
Zone A(B) Maintenance
Regulation enablings
Temperature
MCZN: Maintenance Menu
Zone A(B) Maintenance
Temp. regulation
Hysteresis
9.1.3
Zone work set-point (MCZN module)
The zone work set-point is decided depending on the work mode, manual or automatic (with
programmed weekly time bands), always using the Vgraph zone display.
For the types of work set-point acceptable and for their settings, consult the c-pro CLIMA system
user manual.
Other possibilities also exist to change the work set-point established via Vgraph in the modes listed
below:
9.1.3.1
Variation of the zone work set-point for "climatic curves" (MCZN, MCCT
modules)
By activating the work set-point variation function for “climatic curve”, depending on the external
temperature it is possible (available on the MCCT regulator) to vary the active zone work set-point
value within the minimum and maximum limits that can be set from parameter, in order to adapt the
room temperature to the external climatic conditions, as follows:
-
set the minimum and maximum external temperature limits specific for summer functioning
and winter functioning, within which the variation function of the room set-point is active
-
the room work set-point minimum and maximum variation values are set
-
set the direction of the compensation if direct or inverse for increase or decrease
compensation of the work set-point.
Important parameters:
MCZN: Maintenance Menu
Zone A(B) Maintenance
Regulation enabling
T. Ext set var.
MCZN: Maintenance Menu
Zone A(B) Maintenance
T.ext set variation
MinTExt S
MCZN: Maintenance Menu
Zone A(B) Maintenance
T.ext set variation
MaxTExt S
MCZN: Maintenance Menu
Zone A(B) Maintenance
T.ext set variation
MinTExt Set S
MCZN: Maintenance Menu
Zone A(B) Maintenance
T.ext set variation
MaxTExt Set S
MCZN: Maintenance Menu
Zone A(B) Maintenance
T.ext set variation
ModeTExt Set S
MCZN: Maintenance Menu
Zone A(B) Maintenance
T.ext set variation
MinTExt W
MCZN: Maintenance Menu
Zone A(B) Maintenance
T.ext set variation
MaxTExt W
MCZN: Maintenance Menu
Zone A(B) Maintenance
T.ext set variation
MinTExt Set W
MCZN: Maintenance Menu
Zone A(B) Maintenance
T.ext set variation
MaxTExt Set W
MCZN: Maintenance Menu
Zone A(B) Maintenance
T.ext set variation
ModeTExt Set W