beautypg.com

7 configuration parameters – EVCO c-pro CLIMA sistema Installer manual User Manual

Page 55

background image

C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 55

7.7

Configuration parameters


Below find a list of all configuration parameters contained in the MAINTENANCE menu
(maintenance technician) and INSTALLER managed by the MCDE application.
A brief description is supplied for every parameter, the range of acceptable values, unit of
measurement and the default value proposed.
The menus are structured following the logic given in the respective description paragraphs

8.4.5

and

8.4.6

.

7.7.1

List of MAINTENANCE menu configuration parameters


Label

Parameter description

Default

Min

Max

GENERAL PARAMETERS

General parameters
MCZN assigned

MCZN zone regulator to which the MCDE
dehumidifier module is associated

1

1

8

General parameters
ONOFF(1) d.In.en

Enabling ON OFF digital input
dehumidifier 1

Yes

No

Yes

General parameters
ONOFF(2) d.In.en

Enabling ON OFF digital input
dehumidifier 2

Yes

No

Yes

General parameters
Regulations
Dehumidifyer

Zone assignment (of the associated MCZN regulator)
to which the dehumidification function is associated:
- --- = no Zone associated
- ZA = associated to Zone A
- ZB = associated to Zone B
- ZA+ZB associated to Zone A and Zone B

ZA+ZB

---

ZA+ZB

General parameters
Regulations
Dehum. delay

Delay on activation of the humidifier
(expressed in seconds)

30

0

999


General parameters
Regulations
Booster H

Zone assignment (of the associated MCZN regulator)
to which the heating integration Hot Booster function
is associated:
- --- = no Zone associated
- ZA = associated to Zone A
- ZB = associated to Zone B
- ZA+ZB associated to Zone A and Zone B

ZA+ZB

---

ZA+ZB


General parameters
Regulations
Booster C

Zone assignment (of the associated MCZN regulator)
to which the cooling integration Cold Booster function
is associated:
- --- = no Zone associated
- ZA = associated to Zone A
- ZB = associated to Zone B

ZA+ZB

---

ZA+ZB

BOOSTER

Booster Parameters
Mode

Assignment of the system functioning mode for
activation of heating/cooling integration Booster
functions:
- --- = Booster not enabled
- E = Summer (Cooling Booster only)
- I = Winter (Heating Booster solo)
- E+I = Summer+Winter (Cooling and Heating
Booster only)

E+I

---

E+I