C-PRO CLIMA SISTEMA INSTALLER MANUAL
Page 48
Zone A setup
Terminal units
Type of terminal units present in zone A
- H.T. = High temperature (radiators)
- L.T. = Low temperature (floor heating/cooling)
L.T.
H.T.
L.T.
Zone A setup
Sensor type
Type of probe installed in Zone A
- --- = Not present
- T = Temperature
- T+Set = Temperature + remote set-point variator
- TH = Temperature + humidity
- TH+Set = Temperature + humidity + remote
set-point variator
T
---
TH+Set
Zone A setup
T. probe pos.
Analogue input to which the Zone A temperature probe
is to be associated
- --- = no measurement input (probe not present)
- AIn1 = analogue input 1
- AIn2 = analogue input 2
- AIn3 = analogue input 3
- AIn4 = analogue input 4
AIn1
---
AIn4
Zone A setup
H. probe pos.
Analogue input to which the Zone A humidity transducer
is to be associated
- --- = no measurement input (transd. not present)
- AIn3 = analogue input 3
- AIn4 = analogue input 4
AIn3
---
AIn4
Zone A setup
Rem. set pos.
Analogue input to which the Zone A remote set-point
variator is to be associated
- --- = no measurement input (variator not present)
- AIn1 = analogue input 1
- AIn2 = analogue input 2
- AIn3 = analogue input 3
- AIn4 = analogue input 4
---
---
AIn4
Zone A setup
Reg. type
Enables the regulation mode for Zone A
- OFF = Regulation not active
- E = Regulation only in summer mode (cooling)
- I = Regulation only in winter mode (heating)
- E/I = Regulation in summer and winter mode
E/I
OFF
E/I
Zone A setup
D output cfg
Digital output configuration DO3 associated to Zone A
- ALR = Zona A generic alarm
- BOOST = integration at heating/cooling Zone A
ALR
ALR
BOOST
Zone A setup
Dehum. with H2O
Enable use of delivery line water (circulation pump) for
dehumidification
Yes
No
Yes
Zone A setup
Zone probe signal
Probe type
Type of transducer used to detect humidity
4-20mA
4-20mA
0-5V
Zone A setup
Zone probe signal
Min H. value
Minimum calibration value of the humidity transducer,
corresponding to the 4mA or 0V of the transducer
(expressed in %r.H.)
0.0
0.0
100.0
Zone A setup
Zone probe signal
Max H. value
Maximum calibration value of the humidity transducer,
corresponding to the 20mA or 5V of the transducer
(expressed in %r.H.)
100.0
0.0
100.0
Zone A setup
R.Set calibr.
Calibration points for remote setpoint variator calibration
(expressed in points)
- P1 = maximum negative variation
- P2 =neutral position
- P3 = maximum positive variation
0
999
999
* The same menu is also available for Zone B
REM. DEHUMIDIFIER
Rem. dehumidifyer
Enable control
Enabling of presence of a MCDE module for additional
dehumidifiers associated to the MCZN regulator
No
No
Yes
Rem. dehumidfiyer
CANBUS address
MCDE module CAN address
(assigned automatically by the system)
0
0
55