C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 48

Zone A setup
Terminal units

Type of terminal units present in zone A
- H.T. = High temperature (radiators)
- L.T. = Low temperature (floor heating/cooling)

L.T.

H.T.

L.T.

Zone A setup
Sensor type

Type of probe installed in Zone A
- --- = Not present
- T = Temperature
- T+Set = Temperature + remote set-point variator
- TH = Temperature + humidity
- TH+Set = Temperature + humidity + remote
set-point variator

T

---

TH+Set

Zone A setup
T. probe pos.

Analogue input to which the Zone A temperature probe
is to be associated
- --- = no measurement input (probe not present)
- AIn1 = analogue input 1
- AIn2 = analogue input 2
- AIn3 = analogue input 3
- AIn4 = analogue input 4

AIn1

---

AIn4

Zone A setup
H. probe pos.

Analogue input to which the Zone A humidity transducer
is to be associated
- --- = no measurement input (transd. not present)
- AIn3 = analogue input 3
- AIn4 = analogue input 4

AIn3

---

AIn4

Zone A setup
Rem. set pos.

Analogue input to which the Zone A remote set-point
variator is to be associated
- --- = no measurement input (variator not present)
- AIn1 = analogue input 1
- AIn2 = analogue input 2
- AIn3 = analogue input 3
- AIn4 = analogue input 4

---

---

AIn4

Zone A setup
Reg. type

Enables the regulation mode for Zone A
- OFF = Regulation not active
- E = Regulation only in summer mode (cooling)
- I = Regulation only in winter mode (heating)
- E/I = Regulation in summer and winter mode

E/I

OFF

E/I

Zone A setup
D output cfg

Digital output configuration DO3 associated to Zone A
- ALR = Zona A generic alarm
- BOOST = integration at heating/cooling Zone A

ALR

ALR

BOOST

Zone A setup
Dehum. with H2O

Enable use of delivery line water (circulation pump) for
dehumidification

Yes

No

Yes

Zone A setup
Zone probe signal
Probe type

Type of transducer used to detect humidity

4-20mA

4-20mA

0-5V

Zone A setup
Zone probe signal
Min H. value

Minimum calibration value of the humidity transducer,
corresponding to the 4mA or 0V of the transducer
(expressed in %r.H.)

0.0

0.0

100.0

Zone A setup
Zone probe signal
Max H. value

Maximum calibration value of the humidity transducer,
corresponding to the 20mA or 5V of the transducer
(expressed in %r.H.)

100.0

0.0

100.0

Zone A setup
R.Set calibr.

Calibration points for remote setpoint variator calibration
(expressed in points)
- P1 = maximum negative variation
- P2 =neutral position
- P3 = maximum positive variation

0

999

999

* The same menu is also available for Zone B

REM. DEHUMIDIFIER

Rem. dehumidifyer
Enable control

Enabling of presence of a MCDE module for additional
dehumidifiers associated to the MCZN regulator

No

No

Yes

Rem. dehumidfiyer
CANBUS address

MCDE module CAN address
(assigned automatically by the system)

0

0

55