C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 43


6.4.3

Maintenance menu


The maintenance menu is level 1, i.e. used to insert the maintenance level password or higher in
order to display/modify the parameters present in this branch.


From this menu it is possible to enable and set all features relative to the special control functions of
the zones contained in the MCZN application and precisely:

Entering the ZONES (Zone A / Zone B) menu, the temperature and humidity regulations are
enabled/disabled and the work setpoint remote variation functions, the room climatic curve setpoint
and heating/cooling integration are enabled/disabled and defined via external batteries (present in
the MCDE module), as well as the setting of all user work set-points (including the anti-freeze
setpoint and the regulation hysteresis) and the possibility to calibrate the signals coming from the
measurement inputs.

The MANUAL menu allows to set the functioning of the utilities managed by the application in
manual/automatic mode, thus forcing the state, to test its functionality.

6.4.4

Installer menu


The installer menu is level 2, i.e. used to insert the installer level password or higher in order to
display/modify the parameters present in this branch.


From this menu it is possible to view and set the configuration of the system managed from the
MCZN application.
Entering the I/O CONFIGURATION menu it is possible to set the type of analogue inputs and the
polarity of the digital inputs used in the application.

Entering the GENERAL PARAMETERS menu, the main features present in the controlled zone
regulator are defined, such as the name of the MCZN regulator, the logic positioning of the MCZN
regulator in the controlled system (with consequent value of the CANbus address) and the number
of zones controlled by the MCZN regulator.
As well as the features of the controller in the system, also defined are the presence and type of
Vgraph display connected to it and the features of the serial communication parameters both