C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 39

supervisor or switch-off is requested from key, the power plant goes into the relative OFF state. The
alarms that cause this state are:

-

Delivery 1 probe alarm

-

Delivery 2 probe alarm

The machine works normally again when the alarm has been reset.

5.11

Summer/winter functioning mode


The operational mode can assume the following values:

E/I keyboard parameter Description

S= SUMMER

Summer functioning mode

W= WINTER

Winter functioning mode


There are procedures that allow to set the c-pro CLIMA system functioning mode:

1)

Via the parameter regarding S/W keyboard in the maintenance menu

Setting - Be positioned on the S/W keyboard parameter and, pressing the ENTER key,
modify the value using the UP and DOWN keys. Confirm by pressing ENTER again.

2)

Via supervision protocol (function enabled by parameter S/W BMS)

Setting - Send the operational mode change control via relative state from protocol.
This control has priority with respect to the S/W control from keyboard

3)

Using the Estate/Inverno da ingresso digitale (Summer/winter from digital input) control
(function enabled from S/W D. Input parameter.

Setting - With contact open the unit is in “winter” functioning mode, with contact closed in
“summer” functioning mode.
This control has priority with respect to the S/W control from supervision protocol

4)

Using summer/winter automatic switch-over function (function enabled from S/W Auto
parameter)

Setting - Switch-over from summer to winter takes place when the external temperature
remains above the value established with the T.Ext S parameter for the time established by
the W/S delay parameter
Vice versa, switch-over from winter to summer takes place when the external temperature
remains below the value established with the T.ext W parameter for the time established by
the W/S delay parameter
This control has priority with respect to the S/W control from digital input


As well as selection of the operational mode, a digital output is linked to the summer/winter
functioning mode, which functions as follows:

Functioning mode State of the digital input

S= SUMMER

Summer/Winter output ACTIVE

W= WINTER

Summer/Winter output OFF


A typical application of the summer/winter relay is to automatically inform the chiller/heat pump
unit of the system functioning mode.

Note. For the two manual summer/winter change modes (procedures 1 and 2) it is recommended to
carry out the summer/winter change with the machine off.