C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 77

9.2.9

Delivery anti-freeze protection (MCDE module)

During the winter functioning mode when the system is not running (i.e. in OFF state or with time
bands enabled but in a day when the system is off), however an delivery anti-freeze protection
control remains active
If the external temperature goes below the predefined anti-freeze threshold, the system will function
with special circulation pumps activation in order prevent breakage in the system caused by frozen
pipes.

-

External temperature lower than 4.0°C: delivery pumps always active;

-

External temperature between 5.0 and 1.5 °C: delivery pumps active 10 minutes every 6
hours;

-

External temperature over 1.5°C: delivery pumps off


When the external temperature is between -4.0 and -5.0°C the delivery pumps behaviour depends
on the previous situation.

9.3

Regulation of the zone humidity

(MCZN, MCCT, MCDE modules)

9.3.1

Regulation principle

Whenever the function is enabled and a room humidity transducer is present in zone, during
SUMMER functioning mode when the relative humidity detected by the room humidity transducer
is over the active zone humidity set-point value plus the value of the differential, the MCZN
regulator will activate the corresponding manifold/zone dehumidification valve.

Whenever dehumidification makes use of the delivery water for its action (established via the
relative parameter), the activation of the manifold/zone dehumidification valve generates the same
sequence of activations/controls triggered with zone heating/cooling.
For its functioning, consult the zone temperature regulation part.

9.3.2

Management of the dehumidification manifold/valve (MCZN module)

The manifold/zone dehumidification valve is activated when the value of the room relative
humidity is over the active room humidity set-point + hysteresis value (differential).

Important parameters:
MCZN: Installer menu

Zones

Zone A(B)setup

Sensor type

MCZN: Installer menu

Zones

Zone A(B)setup

H. probe pos.

MCZN: Installer menu

Zones

Zone A(B)setup

Dehum. with H2O

MCZN: Installer menu

Zones

Zone A(B)setup

Zone probe signal

Probe type

MCZN: Installer menu

Zones

Zone A(B)setup

Zone probe signal)

Min H. value

MCZN: Installer menu

Zones

Zone A(B)setup

Zone probe signal)

Max H. value

MCZN: Maintenance Menu

Zone A(B) Maintenance

Regulation enabling

Humidity

MCZN: Maintenance Menu

Zone A(B) Maintenance

Humid. regulation

Hysteresis