9.2.9
Delivery anti-freeze protection (MCDE module)
During the winter functioning mode when the system is not running (i.e. in OFF state or with time
bands enabled but in a day when the system is off), however an delivery anti-freeze protection
control remains active
If the external temperature goes below the predefined anti-freeze threshold, the system will function
with special circulation pumps activation in order prevent breakage in the system caused by frozen
pipes.
-
External temperature lower than 4.0°C: delivery pumps always active;
-
External temperature between 5.0 and 1.5 °C: delivery pumps active 10 minutes every 6
hours;
-
External temperature over 1.5°C: delivery pumps off
When the external temperature is between -4.0 and -5.0°C the delivery pumps behaviour depends
on the previous situation.
9.3
Regulation of the zone humidity
(MCZN, MCCT, MCDE modules)
9.3.1
Regulation principle
Whenever the function is enabled and a room humidity transducer is present in zone, during
SUMMER functioning mode when the relative humidity detected by the room humidity transducer
is over the active zone humidity set-point value plus the value of the differential, the MCZN
regulator will activate the corresponding manifold/zone dehumidification valve.
Whenever dehumidification makes use of the delivery water for its action (established via the
relative parameter), the activation of the manifold/zone dehumidification valve generates the same
sequence of activations/controls triggered with zone heating/cooling.
For its functioning, consult the zone temperature regulation part.
9.3.2
Management of the dehumidification manifold/valve (MCZN module)
The manifold/zone dehumidification valve is activated when the value of the room relative
humidity is over the active room humidity set-point + hysteresis value (differential).
Important parameters:
MCZN: Installer menu
Zones
Zone A(B)setup
Sensor type
MCZN: Installer menu
Zones
Zone A(B)setup
H. probe pos.
MCZN: Installer menu
Zones
Zone A(B)setup
Dehum. with H2O
MCZN: Installer menu
Zones
Zone A(B)setup
Zone probe signal
Probe type
MCZN: Installer menu
Zones
Zone A(B)setup
Zone probe signal)
Min H. value
MCZN: Installer menu
Zones
Zone A(B)setup
Zone probe signal)
Max H. value
MCZN: Maintenance Menu
Zone A(B) Maintenance
Regulation enabling
Humidity
MCZN: Maintenance Menu
Zone A(B) Maintenance
Humid. regulation
Hysteresis