C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 59

8.2

Main page


The main page is displayed during the ON state:




By pressing the DOWN key it is possible to select whether to access the State, pages, the Main
Menu or the System Network, described below.
By pressing ESC key, the controller will go back to the main display of the MCCT thermal power
plant controller.

8.3

State pages


By accessing the STATUS menu from the “Main Page” access the state pages relative to the DHW
circuit (boiler), the two solar panels circuits and the auxiliary circuit (aux1) managed by the MCPS
regulator.

8.3.1

Functioning state of DHW circuit (boiler)

The DHW circuit state page (boiler) will contain the following information:


The DHW (boiler) circuit state pages show, as well as the state of the line described in the previous
illustration, the regulation temperature of the DHW tank (i.e. the lower of the two), the DHW tank
work set-point, the upper and lower temperature of the DHW tank and the days missing to the next
planned running of the antilegionella cycle.

Pressing ENTER on the “>” access the next state page, corresponding with the SOLAR PANELS
CIRCUIT 1.
By pressing ENTER on the “<” access the last state page, i.e. the AUXILIARY 1 CIRCUIT state
page.
When the 60 seconds time-out has passed or by pressing ESC, the controller will go back to the
display of the main ON page.

If flashing, thermal power plant OFFline
DHW tank (lower) temperature (boiler)

MCPS regulator state:
ON = regulation in progress
OFF = regulator OFF
ALARM = MCPS regulator general alarm

If flashing, c-pro CLIMA system in alarm

Line indicating the state of the DHW circuit
Alr = DHW circulation pump block alarm
FL = DHW line flow switch alarm with automatic rearm
FL* = DHW line flow switch alarm with manual rearm
LT = DHW line low water temperature alarm
HT = DHW line high water temperature alarm
Ag = Anti-grip function active
Mn = DHW circulation pump functioning in manual mode

manual