EVCO c-pro CLIMA sistema Installer manual User Manual
Page 13

C-PRO CLIMA SISTEMA INSTALLER MANUAL
Page 13
C-PRO Mega Thermal power plant controller
I/O
Description
Analogue inputs (NTC / 0-5V / 4-20mA)
A/I 1 CT
External air temperature – NTC
A/I 2 CT
Delivery temperature 1 – NTC
A/I 3 CT
Delivery temperature 2 – NTC
Serial ports
Rs485
Rs485 modbus
CANbus
At the c-pro CLIMA system modules
Digital inputs (ON-OFF pocoverial-free contact)
D/I 1 CT
Alarm (block) Boiler
D/I 2 CT
Chiller – Heat pump alarm
D/I 3 CT
Delivery pump 1 flow switch (and/or thermal switch)
D/I 4 CT
Delivery pump 2 flow switch (and/or thermal switch)
D/I 5 CT
Not used
D/I 6 CT
ON-OFF remote
D/I 7 CT
Summer/Winter
Analogue outputs (PWM / 0-10 V / 4-20mA)
A/O 2 CT
Not used
A/O 3 CT
Not used
Digital outputs (Relay)
D/O 1 CT
Delivery 1 circulation pump
D/O 2 CT
Delivery 2 circulation pump
D/O 3 CT
Boiler
D/O 4 CT
Chiller/Heat pump
D/O 5 CT
Summer/winter
D/O 6 CT
Alarm that can be configured
D/O 7 CT
Delivery modulating valve 1 open command
D/O 8 CT
Delivery modulating valve 1 close command
D/O 9 CT
Delivery modulating valve 2 open command
D/O 10 CT
Delivery modulating valve 1 close command