C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 64

8.6

Configuration parameters


Below find a list of all configuration parameters contained in the MAINTENANCE menu
(maintenance technician) and INSTALLER managed by the MCPS application.
A brief description is supplied for every parameter, the range of acceptable values, unit of
measurement and the default value proposed.
The menus are structured following the logic given in the respective description paragraphs

9.4.6

and

9.4.7

.

8.6.1

List of MAINTENANCE menu configuration parameters


Label

Parameter description

Default

Min

Max

GENERAL PARAMETERS

General parameters
Antigrip
Execution day

Antigrip function start day

Monday

Sunday

Saturday

General parameters
Antigrip
Execution hour

Antigrip function start time

2:00

0:00

23:00

General parameters
Probes offset
Upper DHW tank

Boiler upper probe calibration (offset)
(expressed in °C)

0.0

-10.0

10.0

General parameters
Probes offset
Lower DHW tank

Boiler lower probe calibration (offset)
(expressed in °C)

0.0

-10.0

10.0

General parameters
Antilegionella
Enable

Enabling of antilegionella cycle

No

No

Yes

General parameters
Antilegionella
Mode

Antilegionella cycle activation mode
- MONTH = Monthly
- WEEK = Weekly
- DAY = Daily

WEEK

MONTH

DAY

General parameters
Antilegionella
Start hour

Time of antilegionella cycle start
(expressed in hours:minutes)

16:00

0:00

23:00

General parameters
Antilegionella
Day week

Day of the week for antilegionella cycle start
(if weekly activation enabled)

Wednes-

day

Sunday

Saturday

General parameters
Antilegionella
Day month

Day of the month for antilegionella cycle start
(if monthly activation enabled)

15

1

28

General parameters
Antilegionella
Setpoint

Water temperature set-point during the antilegionella
cycle
(expressed in °C)

70.0

0.0

150.0

General parameters
Antilegionella
Duration

Duration of the antilegionella cycle
(expressed in minutes)

60

0

255

MAINTENANCE

Panels Maintenance
Periodic cycle
Interval

Interval between two periodic activation cycles of the
solar panels circulation pumps
(expressed in minutes)

30

0

255

Panels
MAINTENANCE
Periodic cycle
Duration

Duration of the periodic activation cycle of the solar
panels circulation pumps
(expressed in minutes)

10

0

255