8.6
Configuration parameters
Below find a list of all configuration parameters contained in the MAINTENANCE menu
(maintenance technician) and INSTALLER managed by the MCPS application.
A brief description is supplied for every parameter, the range of acceptable values, unit of
measurement and the default value proposed.
The menus are structured following the logic given in the respective description paragraphs
9.4.6
and
9.4.7
.
8.6.1
List of MAINTENANCE menu configuration parameters
Label
Parameter description
Default
Min
Max
GENERAL PARAMETERS
General parameters
Antigrip
Execution day
Antigrip function start day
Monday
Sunday
Saturday
General parameters
Antigrip
Execution hour
Antigrip function start time
2:00
0:00
23:00
General parameters
Probes offset
Upper DHW tank
Boiler upper probe calibration (offset)
(expressed in °C)
0.0
-10.0
10.0
General parameters
Probes offset
Lower DHW tank
Boiler lower probe calibration (offset)
(expressed in °C)
0.0
-10.0
10.0
General parameters
Antilegionella
Enable
Enabling of antilegionella cycle
No
No
Yes
General parameters
Antilegionella
Mode
Antilegionella cycle activation mode
- MONTH = Monthly
- WEEK = Weekly
- DAY = Daily
WEEK
MONTH
DAY
General parameters
Antilegionella
Start hour
Time of antilegionella cycle start
(expressed in hours:minutes)
16:00
0:00
23:00
General parameters
Antilegionella
Day week
Day of the week for antilegionella cycle start
(if weekly activation enabled)
Wednes-
day
Sunday
Saturday
General parameters
Antilegionella
Day month
Day of the month for antilegionella cycle start
(if monthly activation enabled)
15
1
28
General parameters
Antilegionella
Setpoint
Water temperature set-point during the antilegionella
cycle
(expressed in °C)
70.0
0.0
150.0
General parameters
Antilegionella
Duration
Duration of the antilegionella cycle
(expressed in minutes)
60
0
255
MAINTENANCE
Panels Maintenance
Periodic cycle
Interval
Interval between two periodic activation cycles of the
solar panels circulation pumps
(expressed in minutes)
30
0
255
Panels
MAINTENANCE
Periodic cycle
Duration
Duration of the periodic activation cycle of the solar
panels circulation pumps
(expressed in minutes)
10
0
255