C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 67

General parameters
CANbus address

CANbus serial address

17

0

255

General parameters
Baud rate

CANbus communication speed (baud rate)
-20Kbit
-50Kbit
-125Kbit
-500Kbit

125Kbit

20Kbit

500Kbit

General parameters
MODBUS network
Idx

Modbus serial address

1

1

247

General parameters
MODBUS network
Baud

Modbus communication speed (baud rate)
- 1200Kb
- 2400Kb
- 4800Kb
- 9600Kb
- 19200Kb

9600Kb

1200Kb

19200Kb

General parameters
MODBUS network
Parity

Type of Modbus communication parity
- NO
- ODD
- EVEN

EVEN

NO

EVEN

General parameters
MODBUS network
Stop

Modbus communication Bit Stop position

1b

1b

2b

SOLAR PANELS

Solar panels
Probes offset
Panel 1

Solar panel 1 water temperature transducer (offset)
calibration
(expressed in °C)

0.0

-10.0

10.0

Solar panels
Probes offset
Panel 2

Solar panel 2 water temperature transducer (offset)
calibration
(expressed in °C)

0.0

-10.0

10.0

Solar panels
P.1 sensor
Min.

Solar panel 1 water temperature transducer minimum
calibration value
(expressed in °C)

0.0

-100.0

300.0

Solar panels
P.1 sensor
Max.

Solar panel 1 water temperature transducer maximum
calibration value
(expressed in °C)

200.0

-100.0

300.0

Solar panels
P.2 sensor
Min.

Solar panel 2 water temperature transducer minimum
calibration value
(expressed in °C)

0.0

-100.0

300.0

Solar panels
P.2 sensor
Max.

Solar panel 2 water temperature transducer maximum
calibration value
(expressed in °C)

200.0

-100.0

300.0

8.7

State of the unit

The state of the MCPS regulator is given by the state of the MCCT thermal power plant regulator.