C-PRO CLIMA SISTEMA INSTALLER MANUAL
Page 16
3.3.4
Solar panels electric connections (MCPS).
C-PRO Micro solar panels controller
I/O
Description
Analogue inputs (NTC / 0-5V / 4-20mA)
A/I 1 PS
DHW tank temperature (upper) (NTC)
A/I 2 PS
DHW tank lower temperature (NTC)
A/I 3 PS
Auxiliary temperature 1 (NTC)
Solar panel 2 temperature (4-20 mA).
A/I 4 PS
Solar panel 1 temperature (4-20 mA).
Serial ports
TTL (485)
TTL with EVIF external interface becomes RS485 Modbus RTU
CANbus
At the c-pro CLIMA system modules
Digital inputs (ON-OFF pocoverial-free contact)
D/I 1 PS
Solar panels 1 circuit pump (thermal) flow switch
D/I 2 PS
Solar panels 2 circuit pump (thermal) flow switch
D/I 3 PS
DHW circuit pump (thermal) flow switch
D/I 4 PS
Auxiliary system circuit pump (thermal) flow switch
D/I 5 PS
Not used
Digital outputs (Relay)
D/O 1 PS
Solar panels 1 circuit pump
D/O 2 PS
Solar panels 2 circuit pump
D/O 3 PS
DHW circuit pump
D/O 4 PS
Alarm (that can be configured)
D/O 5 PS
Auxiliary 1 circuit pump
Anti-stagnation emergency (cover opening)
D/O 6 PS
Anti-stagnation emergency (heat disposal/cover opening)
Anti-stagnation emergency (cover closing)