beautypg.com

EVCO c-pro CLIMA sistema Installer manual User Manual

Page 16

background image

C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 16

3.3.4

Solar panels electric connections (MCPS).

C-PRO Micro solar panels controller
I/O

Description

Analogue inputs (NTC / 0-5V / 4-20mA)

A/I 1 PS

DHW tank temperature (upper) (NTC)

A/I 2 PS

DHW tank lower temperature (NTC)

A/I 3 PS

Auxiliary temperature 1 (NTC)
Solar panel 2 temperature (4-20 mA).

A/I 4 PS

Solar panel 1 temperature (4-20 mA).

Serial ports

TTL (485)

TTL with EVIF external interface becomes RS485 Modbus RTU

CANbus

At the c-pro CLIMA system modules

Digital inputs (ON-OFF pocoverial-free contact)

D/I 1 PS

Solar panels 1 circuit pump (thermal) flow switch

D/I 2 PS

Solar panels 2 circuit pump (thermal) flow switch

D/I 3 PS

DHW circuit pump (thermal) flow switch

D/I 4 PS

Auxiliary system circuit pump (thermal) flow switch

D/I 5 PS

Not used

Digital outputs (Relay)

D/O 1 PS

Solar panels 1 circuit pump

D/O 2 PS

Solar panels 2 circuit pump

D/O 3 PS

DHW circuit pump

D/O 4 PS

Alarm (that can be configured)

D/O 5 PS

Auxiliary 1 circuit pump
Anti-stagnation emergency (cover opening)

D/O 6 PS

Anti-stagnation emergency (heat disposal/cover opening)
Anti-stagnation emergency (cover closing)