C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 45

6.7

Configuration parameters


Below find a list of all configuration parameters contained in the MAINTENANCE menu and
INSTALLER managed by the MCZN application.
A brief description is supplied for every parameter, the range of acceptable values, unit of
measurement and the default value proposed.
The menus are structured following the logic given in the respective description paragraphs

7.4.3

and

7.4.4

.

6.7.1

List of MAINTENANCE menu configuration parameters


Label

Parameter description

Default

Min

Max

ZONE A MAINTENANCE

Zone A Maintenance
Regulation enabling
Temperature

Enabling of Zone A temperature regulation

YES

NO

YES

Zone A Maintenance
Regulation enabling
Humidity

Enabling of Zone A humidity regulation

NO

NO

YES

Zone A Maintenance
Regulation enabling
T.Ext.set var

Enabling of Zone A room setpoint "climatic curve"
function

NO

NO

YES

Zone A Maintenance
Regulation enabling
T. integration

Enabling of Zone A heating/cooling integration"
function (via MCDE module)
- --- = Function disabled
- S = Cooling integration (summer)
- W = Heating integration (winter)
- S+W = Cooling/heating integration

(summer + winter)

---

---

S+W

Zone A Maintenance
Temp. regulation
COMFORT [S]

Zone A summer Comfort time band pre-defined
temperature set-point (expressed in °C)

23.0

10.0

30.0

Zone A Maintenance
Temp. regulation
ECONOMY [S]

Zone A summer Economy time band pre-defined
temperature set-point (expressed in °C)

26.0

10.0

30.0

Zone A Maintenance
Temp. regulation
COMFORT [W]

Zone A winter Comfort time band pre-defined
temperature set-point (expressed in °C)

19.0

10.0

30.0

Zone A Maintenance
Temp. regulation
ECONOMY [W]

Zone A winter Economy time band pre-defined
temperature set-point (expressed in °C)

16.0

10.0

30.0

Zone A Maintenance
Temp. Regulation
ANTIFREEZE

Anti-freeze time band temperature set-point in winter
mode
Zone A (expressed in °C)

3.0

-10.0

30.0

Zone A Maintenance
Temp. regulation
Min Set Ofs

Work temperature set-point maximum negative
variation by Zone A remote set-point variator
(expressed in °C)

-5.0

-10.0

10.0

Zone A Maintenance
Temp. regulation
Max Set Ofs

Work temperature set-point maximum positive
variation by Zone A remote set-point variator
(expressed in °C)

5.0

-10.0

10.0

Zone A Maintenance
Temp. regulation
Hysteresis

Zone A room temperature regulation hysteresis
(differential) relative to the work set-point
(expressed in °C)

1.0

0.0

99.9

Zone A Maintenance
Temp. integration
Winter delta

Difference between room temperature and work set-
point due to activation of the winter Zone A
“integration to heating” function (expressed in °C)

1.0

0.0

10.0