C-PRO CLIMA SISTEMA INSTALLER MANUAL
Page 45
6.7
Configuration parameters
Below find a list of all configuration parameters contained in the MAINTENANCE menu and
INSTALLER managed by the MCZN application.
A brief description is supplied for every parameter, the range of acceptable values, unit of
measurement and the default value proposed.
The menus are structured following the logic given in the respective description paragraphs
7.4.3
and
7.4.4
.
6.7.1
List of MAINTENANCE menu configuration parameters
Label
Parameter description
Default
Min
Max
ZONE A MAINTENANCE
Zone A Maintenance
Regulation enabling
Temperature
Enabling of Zone A temperature regulation
YES
NO
YES
Zone A Maintenance
Regulation enabling
Humidity
Enabling of Zone A humidity regulation
NO
NO
YES
Zone A Maintenance
Regulation enabling
T.Ext.set var
Enabling of Zone A room setpoint "climatic curve"
function
NO
NO
YES
Zone A Maintenance
Regulation enabling
T. integration
Enabling of Zone A heating/cooling integration"
function (via MCDE module)
- --- = Function disabled
- S = Cooling integration (summer)
- W = Heating integration (winter)
- S+W = Cooling/heating integration
(summer + winter)
---
---
S+W
Zone A Maintenance
Temp. regulation
COMFORT [S]
Zone A summer Comfort time band pre-defined
temperature set-point (expressed in °C)
23.0
10.0
30.0
Zone A Maintenance
Temp. regulation
ECONOMY [S]
Zone A summer Economy time band pre-defined
temperature set-point (expressed in °C)
26.0
10.0
30.0
Zone A Maintenance
Temp. regulation
COMFORT [W]
Zone A winter Comfort time band pre-defined
temperature set-point (expressed in °C)
19.0
10.0
30.0
Zone A Maintenance
Temp. regulation
ECONOMY [W]
Zone A winter Economy time band pre-defined
temperature set-point (expressed in °C)
16.0
10.0
30.0
Zone A Maintenance
Temp. Regulation
ANTIFREEZE
Anti-freeze time band temperature set-point in winter
mode
Zone A (expressed in °C)
3.0
-10.0
30.0
Zone A Maintenance
Temp. regulation
Min Set Ofs
Work temperature set-point maximum negative
variation by Zone A remote set-point variator
(expressed in °C)
-5.0
-10.0
10.0
Zone A Maintenance
Temp. regulation
Max Set Ofs
Work temperature set-point maximum positive
variation by Zone A remote set-point variator
(expressed in °C)
5.0
-10.0
10.0
Zone A Maintenance
Temp. regulation
Hysteresis
Zone A room temperature regulation hysteresis
(differential) relative to the work set-point
(expressed in °C)
1.0
0.0
99.9
Zone A Maintenance
Temp. integration
Winter delta
Difference between room temperature and work set-
point due to activation of the winter Zone A
“integration to heating” function (expressed in °C)
1.0
0.0
10.0