EVCO c-pro CLIMA sistema Installer manual User Manual
Page 46

C-PRO CLIMA SISTEMA INSTALLER MANUAL
Page 46
Zone A Maintenance
Temp. integration
Winter delay
Delay on activation of the summer Zone A "integration
to heating" function
(expressed in minutes)
5
1
255
Zone A Maintenance
Temp. integration
Summer delta
Difference between room temperature and work set-
point due to activation of the summer Zone A
“integration to cooling” function (expressed in °C)
0.0
0.0
10.0
Zone A Maintenance
Temp. integration
Summer delay
Delay on activation of the summer Zone A "integration
to cooling" function
(expressed in minutes)
5
1
255
Zone A Maintenance
T.Ext.Set variation
MinTExt S
Minimum external temperature in summer for summer
Zone A "climatic curve" calculation
(expressed in °C)
12.0
0.0
60.0
Zone A Maintenance
T.Ext.Set variation
MaxTExt S
Maximum external temperature in summer for summer
Zone A "climatic curve" calculation
(expressed in °C)
35.0
0.0
60.0
Zone A Maintenance
T.Ext.Set variation
MinTExt Set W
Summer work temperature set-point maximum
negative variation for zone A summer “climatic curve”
calculation (expressed in °C)
-5.0
-10.0
10.0
Zone A Maintenance
T.Ext.Set variation
MaxTExt Set W
Summer work temperature set-point maximum positive
variation for zone A summer “climatic curve”
calculation (expressed in °C)
5.0
-10.0
10.0
Zone A Maintenance
T.Ext.Set variation
Mode TExt.W
Calculation method of the summer
Zone A "climatic curve":
- DIR. = Direct
- INV. = Inverse
DIR.
DIR.
INV.
Zone A Maintenance
T.Ext.Set variation
MinTExt W
Minimum external temperature in winter for winter
Zone A "climatic curve" calculation
(expressed in °C)
-5.0
-30.0
40.0
Zone A Maintenance
T.Ext.Set variation
MaxTExt W
Maximum external temperature in winter for winter
Zone A "climatic curve" calculation
(expressed in °C)
12.0
-30.0
40.0
Zone A Maintenance
T.Ext.Set variation
MinTExt Set W
Winter work temperature set-point maximum negative
variation for zone A winter “climatic curve”
calculation
(expressed in °C)
5.0
-10.0
10.0
Zone A Maintenance
T.Ext.Set variation
MaxTExt Set W
Winter work temperature set-point maximum positive
variation for zone A winter “climatic curve”
calculation
(expressed in °C)
-5.0
-10.0
10.0
Zone A Maintenance
T.Ext.Set variation
Mode TExt.W
Calculation method of the winter Zone A "climatic
curve"
- DIR. = Direct
- INV. = Inverse
DIR.
DIR.
INV.
Zone A Maintenance
Humid. regulation
COMFORT
Zone A Comfort time band pre-defined humidity set-
point
(expressed in %r.H.)
50.0
0.0
100.0
Zone A Maintenance
Humid. regulation
ECONOMY
Zone A Economy time band pre-defined humidity set-
point
(expressed in %r.H.)
50.0
0.0
100.0
Zone A Maintenance
Humid. regulation
Hysteresis
Zone A room humidity regulation hysteresis
(differential) relative to the work set-point
(expressed in %r.H.)
5.0
0.0
99.9
Zone A Maintenance
Probes calibration
Temperature
Zone A room temperature probe calibration
(expressed in °C)
0.0
-10.0
10.0
Zone A Maintenance
Probes calibration
Humidity
Zone A room humidity transducer calibration
(expressed in %r.H.)
0.0
-10.0
10.0
Zone A Maintenance
Probes calibration
Rem. Set.
Zone A remote set-point variator calibration
(expressed in points)
0
-100
100