C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 46

Zone A Maintenance
Temp. integration
Winter delay

Delay on activation of the summer Zone A "integration
to heating" function
(expressed in minutes)

5

1

255

Zone A Maintenance
Temp. integration
Summer delta

Difference between room temperature and work set-
point due to activation of the summer Zone A
“integration to cooling” function (expressed in °C)

0.0

0.0

10.0

Zone A Maintenance
Temp. integration
Summer delay

Delay on activation of the summer Zone A "integration
to cooling" function
(expressed in minutes)

5

1

255

Zone A Maintenance
T.Ext.Set variation
MinTExt S

Minimum external temperature in summer for summer
Zone A "climatic curve" calculation
(expressed in °C)

12.0

0.0

60.0

Zone A Maintenance
T.Ext.Set variation
MaxTExt S

Maximum external temperature in summer for summer
Zone A "climatic curve" calculation
(expressed in °C)

35.0

0.0

60.0

Zone A Maintenance
T.Ext.Set variation
MinTExt Set W

Summer work temperature set-point maximum
negative variation for zone A summer “climatic curve”
calculation (expressed in °C)

-5.0

-10.0

10.0

Zone A Maintenance
T.Ext.Set variation
MaxTExt Set W

Summer work temperature set-point maximum positive
variation for zone A summer “climatic curve”
calculation (expressed in °C)

5.0

-10.0

10.0

Zone A Maintenance
T.Ext.Set variation
Mode TExt.W

Calculation method of the summer

Zone A "climatic curve":
- DIR. = Direct
- INV. = Inverse

DIR.

DIR.

INV.

Zone A Maintenance
T.Ext.Set variation
MinTExt W

Minimum external temperature in winter for winter
Zone A "climatic curve" calculation
(expressed in °C)

-5.0

-30.0

40.0

Zone A Maintenance
T.Ext.Set variation
MaxTExt W

Maximum external temperature in winter for winter
Zone A "climatic curve" calculation
(expressed in °C)

12.0

-30.0

40.0

Zone A Maintenance
T.Ext.Set variation
MinTExt Set W

Winter work temperature set-point maximum negative
variation for zone A winter “climatic curve”
calculation
(expressed in °C)

5.0

-10.0

10.0

Zone A Maintenance
T.Ext.Set variation
MaxTExt Set W

Winter work temperature set-point maximum positive
variation for zone A winter “climatic curve”
calculation
(expressed in °C)

-5.0

-10.0

10.0

Zone A Maintenance
T.Ext.Set variation
Mode TExt.W

Calculation method of the winter Zone A "climatic
curve"
- DIR. = Direct
- INV. = Inverse

DIR.

DIR.

INV.

Zone A Maintenance
Humid. regulation
COMFORT

Zone A Comfort time band pre-defined humidity set-
point
(expressed in %r.H.)

50.0

0.0

100.0

Zone A Maintenance
Humid. regulation
ECONOMY

Zone A Economy time band pre-defined humidity set-
point
(expressed in %r.H.)

50.0

0.0

100.0

Zone A Maintenance
Humid. regulation
Hysteresis

Zone A room humidity regulation hysteresis
(differential) relative to the work set-point
(expressed in %r.H.)

5.0

0.0

99.9

Zone A Maintenance
Probes calibration
Temperature

Zone A room temperature probe calibration
(expressed in °C)

0.0

-10.0

10.0

Zone A Maintenance
Probes calibration
Humidity

Zone A room humidity transducer calibration
(expressed in %r.H.)

0.0

-10.0

10.0

Zone A Maintenance
Probes calibration
Rem. Set.

Zone A remote set-point variator calibration
(expressed in points)

0

-100

100