General parameters
MODBUS network
Idx
Modbus serial address
1
1
247
General parameters
MODBUS network
Baud
Modbus communication speed (baud rate)
- 1200Kb
- 2400Kb
- 4800Kb
- 9600Kb
- 19200Kb
9600Kb
1200Kb
19200Kb
General parameters
MODBUS network
Parity
Type of Modbus communication parity
- NO
- ODD
- EVEN
EVEN
NO
EVEN
General parameters
MODBUS network
Stop
Modbus communication Bit Stop position
1b
1b
2b
CO2
CO2 regulation
CO2 control en.
Enabling of CO2 transducer reading
No
No
Yes
CO2 regulation
Min. limit
Minimum calibration value of the CO2 transducer,
corresponding to the 4mA or 0V of the transducer
(expressed in ppm)
0
0
5000
CO2 regulation
Max. limit
Maximum calibration value of the CO2 transducer,
corresponding to the 20mA or 5V of the transducer
(expressed in ppm)
2000
0
5000
DEHUMIDIFYER
Dehumidifyer
Dehum. type
Type of dehumidifier managed:
0 = dehumidifier type 0
1 = dehumidifier type 1
2 = dehumidifier type 2
1
0
2
Dehumidifier
Boost1 T.in en.
Enabling of dehumidifier 1 input temperature limit
function due to activation of Booster 1 function.
No
No
Yes
Dehumidifier
Boost2 T.in en.
Enabling of dehumidifier 2 input temperature limit
function due to activation of Booster 1 function.
No
No
Yes
7.8
State of the unit
The state of the MCDE regulator is given by the state of the MCZN associated regulator.