2 list of installer menu configuration parameters – EVCO c-pro CLIMA sistema Installer manual User Manual
Page 56

C-PRO CLIMA SISTEMA INSTALLER MANUAL
Page 56
Booster Parameters
Booster H
Zone assignment (of the associated MCZN regulator)
to which the heating integration Hot Booster function
is associated:
- --- = no Zone associated
- ZA = associated to Zone A
- ZB = associated to Zone B
- ZA+ZB associated to Zone A and Zone B
ZA+ZB
---
ZA+ZB
Booster Parameters
Booster C
Zone assignment (of the associated MCZN regulator)
to which the cooling integration Cold Booster function
is associated:
- --- = no Zone associated
- ZA = associated to Zone A
- ZB = associated to Zone B
- ZA+ZB associated to Zone A and Zone B
ZA+ZB
---
ZA+ZB
Booster Parameters
Set deh1 in
Minimum input temperature dehumidifier 1 setpoint
for enabling of Heating Booster
(expressed in °C)
35.0
0.0
100.0
Booster Parameters
Set deh2 in
Minimum input temperature dehumidifier 2 setpoint
for enabling of Heating Booster
(expressed in °C)
35.0
0.0
100.0
Booster Parameters
Dehum. activ.
Link between the activation of the booster output and
the activation of the dehumidifier output
Yes
No
Yes
CO2
CO2 parameters
Enable reg.
Enabling regulation of the CO2 level
Yes
No
Yes
CO2 parameters
Dumper mode
Fresh air dumper functioning mode:
- --- = not enabled
- CLOSED = fixed
- MODUL. = modulating
- OPEN = fixed
MODUL.
---
OPEN
CO2 parameters
Setpoint
Room maximum CO2 level setpoint due to dumper
opening
(expressed in parts per million)
0
0
2000
CO2 regulation
Hysteresis
Hysteresis (differential) relative to the CO2 setpoint
(expressed in parts per million)
10
0
100
7.7.2
List of INSTALLER menu configuration parameters
Label
Parameter description
Default
Min
Max
I/O CONFIGURATION
I/O configuration
AIn3
AIn3 analogue input configuration type:
- 4-20mA
- 0-5V
4-20mA
4-20mA
0-5V
I/O configuration
DIn
Type of contact for digital inputs
NA = normally open
NC = normally closed
N.O.
N.C.
N.O.
GENERAL PARAMETERS
General parameters
MCZN assigned
MCZN zone regulator to which the MCDE module is
associated
1
1
8
General parameters
CANBUS address
CANbus serial address
0
0
255
General parameters
Baud Rate
CANbus communication speed (baud rate)
-20Kbit
-50Kbit
-125Kbit
-500Kbit
125Kbit
20Kbit
500Kbit