2 list of installer menu configuration parameters – EVCO c-pro CLIMA sistema Installer manual User Manual

Page 66

background image

C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 66

Aux 1 Maintenance
Mode

Auxiliary circuit 1 circulation pump regulation mode:
- CONT. = Continuous
- T.RICH. = On temperature request

T.RICH.

CONT.

T.RICH.

DHW MANAGEMENT

DHW maintenance
Delay

Delay on activation of the DHW circuit pump
(expressed in seconds)

30

0

255

FLOW SWITCHES

Flow switches
Alr ON delay

Delay on activation of the flow switch alarm from
system start-up
(expressed in seconds)

3
0

0

255

Flow switches
Alr RUN delay

Delay on activation of the flow switch alarm with
system in normal conditions
(expressed in seconds)

5

0

255

Flow switches
Auto reset n°

Maximum number of flow switch alarms with
automatic rearm for passage to manual rearm

3

0

255

8.6.2

List of INSTALLER menu configuration parameters


Label

Parameter description

Default

Min

Max

I/O CONFIGURATION

I/O configuration
AIn 1

Type of analogue input configured for AIn2:
read only parameter

NTC

NTC

NTC

I/O configuration
AIn 2

Type of analogue input configured for AIn2:
read only parameter

NTC

NTC

NTC

I/O configuration
AIn 3

Type of analogue input configured for AIn3:
read only parameter

NTC

NTC

4-20mA

I/O configuration
AIn 4

Type of analogue input configured for AIn4:
read only parameter

4-20mA

4-20mA

4-20mA

I/O configuration
DIn

Type of contact for digital inputs:
NO = normally open
NC = normally closed

N.C.

N.C.

N.O.

GENERAL PARAMETERS

General parameters
Solar panels

Number of solar panel circuits present in the plant

1

0

2

General parameters
Aux 1 circuit

Enabling of auxiliary circuit 1 (aux1)

No

No

Yes

General parameters
DHW probes
Upper probe en.

Enabling of DHW tank upper probe (boiler)

Yes

No

Yes

General parameters
DHW probes
Upper probe en.

Enabling of DHW tank lower probe (boiler)

Yes

No

Yes

General parameters
Pumps alarm setup
Solar pump 1

Type of digital input for protection of solar panel circuit
circulation pump 1:
THERMAL = Protection input
FLOW = Flow switch

FLOW

THER-

MAL

FLOW

General parameters
Pumps alarm setup
Solar pump 2

Type of digital input for protection of solar panel circuit
circulation pump 2:
THERMAL = Protection input
FLOW = Flow switch

FLOW

THER-

MAL

FLOW

General parameters
Pumps alarms cfg
DHW pump

Type of digital input for protection of DHW circuit
circulation pump:
THERMAL = Protection input
FLOW = Flow switch

FLOW

THER-

MAL

FLOW

General parameters
Pumps alarms cfg
AUX1 pump

Type of digital input for protection of AUX1 circuit
circulation pump:
THERMAL = Protection input
FLOW = Flow switch

FLOW

THER-

MAL

FLOW