beautypg.com

8 state pages – EVCO c-pro CLIMA sistema Installer manual User Manual

Page 32

background image

C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 32

5.8

State pages


By accessing the state pages from the ON main page, access the following four screens representing
the machine states of the c-pro mega MCCT controller and the entire controlled system.

5.8.1

Delivery line L1 and delivery line L2 state page


The state pages of the Delivery line 1 and 2 show, as well as the state of the line described in the
previous illustration, the opening percentage of the mixing valve, the delivery line water
temperature,the active work set-point and the calculation of the dew point for the corresponding
line.

Pressing ENTER on the “>” access the next state page, corresponding with delivery line 2.
By pressing ENTER on the “>” again, access the next state page, i.e. the SOLAR PANELS
state/access page.
When the 30 seconds time-out has passed or by pressing ESC, the controller will go back to the
display of the main ON page.

5.8.2

State page and access to the MCPS solar panels module


The state page and access to the MCPS solar panels module shows, as well as the network state of
the MCPS regulator, described in the previous element, the temperature of the boiler (DHW tank).

Pressing ENTER on the “>” in the top right of the screen, access the next state page, i.e. the
state/access page to the ZONE REGULATORS modules.
Pressing ENTER on the MCPS module state (with MCPS module enabled and on-line) the MCPS
application can be accessed.
When the 30 seconds time-out has passed or by pressing ESC, the controller will go back to the
display of the main ON page.





Line indicating the state of the L1/L2 delivery line:
P1 = circulation pump P1 activated
Alr = P1 circulation pump block alarm
FL = delivery line 1 flow switch alarm with automatic rearm
* = delivery line 1 flow switch alarm with manual rearm running
Fs = delivery line 1 flow switch with manual rearm function active
LT = delivery line low water temperature alarm
HT = delivery line high water temperature alarm
Fz = Anti-freeze function active
Ag = Anti-grip function active
Mn = P1 circulation pump functioning in manual mode

Line indicating the state of the MCPS solar panels module
MCPS = MCPS module enabled and on-line
MCPS OFFLine = MCPS module enabled but off-line
No MCPS = MCPS module not enabled