Pumps flow switches
Run
Delay time on activation of the alarms relative to the 1
and 2 delivery flow switches with system in normal
conditions (expressed in seconds)
5
0
255
Pumps flow switches
Nr. alarms/hour
Maximum number of alarms/hour relative to delivery
flow switches 1 and 2 for passage to manual rearm
3
0
255
Network
management
Zone modul.
enabling
Temporary MCZN disabling/enabling
X = enabled
O = not enabled
O
X
O
DELIVERY LINES
Maintenance L1
Pump mode
Functioning mode of the circulation pump 1
CONT. = continuous
TRICH. = on temperature request
TRICH.
CONT.
TRICH.
Maintenance L1
Pump management
Alarm delay
Delay time on activation of the alarm relative to the
circulation pump 1 (expressed in seconds)
0
0
255
Maintenance L1
Pump management
ON delay
Delay time on switch on of the circulation pump 1
(expressed in seconds)
30
0
255
Maintenance L1
Pump management
OFF delay
Delay time on switch-off value change of mixing valve 1
(expressed in seconds)
30
0
255
Maintenance L1
Pump management
Mix.vlv. delay
Delay time on opening value change of mixing valve 1
(expressed in seconds)
30
0
255
Maintenance L1
Pump management
CH-HP delay
Delay time on activation of the chiller/heat pump
(expressed in seconds)
60
0
255
Maintenance L1
Pump management
Antigrip enab.
Enabling of the line 1 antigrip function
Yes
No
Yes
Maintenance L1
Temp. regulation
Setpoint S LT
L.T. line 1 summer delivery set-point (expressed in °C)
18.0
7.0
30.0
Maintenance L1
Temp. regulation
Setpoint W LT
H.T. line 1 winter delivery set-point (expressed in °C)
30.0
20.0
90.0
Maintenance L1
Temp. regulation
Setpoint S HT
H.T. line 1 summer delivery set-point (expressed in °C)
12.0
5.0
30.0
Maintenance L1
Temp. regulation
Setpoint W HT
H.T. line 1 winter delivery set-point
(expressed in °C)
60.0
25.0
90.0
Maintenance L1
T. regulation
Dew offset
Offset (differential) to add to the delivery line 1 dew
point, calculated to obtain the delivery work set-point
value in Summer mode
(expressed in °C)
3.0
0.0
10.0
Maintenance L1
Mixing valve S
Mode
Summer mixing valve 1 functioning mode
- Closed
- Modulating
- Opened
MODUL.
CLOSED
OPENED
Maintenance L1
Mixing valve S
Min.Ext.T.
Minimum external temperature in summer for the
calculation of the delivery 1 floating set-point (expressed
in °C)
10.0
0.0
30.0
Maintenance L1
Mixing valve S
Max.Ext.T.
Maximum external temperature in summer for the
calculation of the delivery 1 floating set-point (expressed
in °C)
30.0
10.0
60.0
Maintenance L1
Mixing valve S
Setpoint 1
Value of the floating delivery 1 set-point relative to the
minimum external temperature in Summer mode
(expressed in °C)
12.0
0.0
40.0