C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 34

Pumps flow switches
Run

Delay time on activation of the alarms relative to the 1
and 2 delivery flow switches with system in normal
conditions (expressed in seconds)

5

0

255

Pumps flow switches
Nr. alarms/hour

Maximum number of alarms/hour relative to delivery
flow switches 1 and 2 for passage to manual rearm

3

0

255

Network
management
Zone modul.
enabling

Temporary MCZN disabling/enabling
X = enabled
O = not enabled

O

X

O

DELIVERY LINES

Maintenance L1
Pump mode

Functioning mode of the circulation pump 1
CONT. = continuous
TRICH. = on temperature request

TRICH.

CONT.

TRICH.

Maintenance L1
Pump management
Alarm delay

Delay time on activation of the alarm relative to the
circulation pump 1 (expressed in seconds)

0

0

255

Maintenance L1
Pump management
ON delay

Delay time on switch on of the circulation pump 1
(expressed in seconds)

30

0

255

Maintenance L1
Pump management
OFF delay

Delay time on switch-off value change of mixing valve 1
(expressed in seconds)

30

0

255

Maintenance L1
Pump management
Mix.vlv. delay

Delay time on opening value change of mixing valve 1
(expressed in seconds)

30

0

255

Maintenance L1
Pump management
CH-HP delay

Delay time on activation of the chiller/heat pump
(expressed in seconds)

60

0

255

Maintenance L1
Pump management
Antigrip enab.

Enabling of the line 1 antigrip function

Yes

No

Yes

Maintenance L1
Temp. regulation
Setpoint S LT

L.T. line 1 summer delivery set-point (expressed in °C)

18.0

7.0

30.0

Maintenance L1
Temp. regulation
Setpoint W LT

H.T. line 1 winter delivery set-point (expressed in °C)

30.0

20.0

90.0

Maintenance L1
Temp. regulation
Setpoint S HT

H.T. line 1 summer delivery set-point (expressed in °C)

12.0

5.0

30.0

Maintenance L1
Temp. regulation
Setpoint W HT

H.T. line 1 winter delivery set-point
(expressed in °C)

60.0

25.0

90.0

Maintenance L1
T. regulation
Dew offset

Offset (differential) to add to the delivery line 1 dew
point, calculated to obtain the delivery work set-point
value in Summer mode

(expressed in °C)

3.0

0.0

10.0

Maintenance L1
Mixing valve S
Mode

Summer mixing valve 1 functioning mode
- Closed
- Modulating
- Opened

MODUL.

CLOSED

OPENED

Maintenance L1
Mixing valve S
Min.Ext.T.

Minimum external temperature in summer for the
calculation of the delivery 1 floating set-point (expressed
in °C)

10.0

0.0

30.0

Maintenance L1
Mixing valve S
Max.Ext.T.

Maximum external temperature in summer for the
calculation of the delivery 1 floating set-point (expressed
in °C)

30.0

10.0

60.0

Maintenance L1
Mixing valve S
Setpoint 1

Value of the floating delivery 1 set-point relative to the
minimum external temperature in Summer mode
(expressed in °C)

12.0

0.0

40.0