5-13

- IV Series User’s Manual (Field Network) -

Data I/O communication setting method

11

Open [PROFINET IO] - [Additional Field

Devices] - [Sensors] - [Keyence Vision

Sensors] from [Hardware Catalog] in the

[HW Config] window, and then drag &

drop [IV-xxxx] onto [PROFINET-IO-System]

in the Station Window.

The IV series will be added to the Station
Window; and all modules available for the IV
series will be added automatically.

If [PROFINET-IO-System] is not displayed
on the Station Window, right-click [PN-IO]
of the CPU and select [Insert PROFINET IO
System].

12

Double-click the IV series icon in the [HW

Config] window.

The [Properties - IV series] window will appear.

13

Enter the same character string as the

PROFINET device name of the IV series to

be connected into the [Device name] field.

14

Click the [Ethernet] button.

The [Properties - Ethernet interface IV series]
window will appear.

15

Enter the IP address for the IV series to be

connected into the [IP address] field.

16

Click the [OK] button to return to the [HW

config] window.

5

Data I/O communication