Data I/O communication setting method

This following explains the setting method when
using the data I/O communication.

yTo control the IV series using the PROFINET

communication, select [Network connection] for the

sensor connection setting. When connected directly, the

field network settings will be greyed out and disabled.

y

The PROFINET function will stop if the scanner is

connected directly while the PROFINET function

is in use. To use the PROFINET function again,

you need to restart the sensor.

y

If you have modified the protocol settings, the

connection with the sensor will be terminated and

then restarted.

Setting the IV series

You can configure the following settings for the IV series
using the monitor (IV-M30) or IV-Navigator (IV-H1).

When settings on the monitor (IV-M30)

Set the field network settings of the sensor to
[PROFINET].

1

Touch the [Sensor expansion settings]

button on the sensor settings menu screen.

2

Touch the [Environment setting] button,

followed by the [Network expansion

setting] button.

3

Touch the [Settings] button for the field

network.

4

Select [PROFINET] for the protocol.

5

Select [Enabled] if you wish to enable the

data handshake control.

y

If the protocol is set to [Disabled], the

settings will be greyed out and disabled.

y

If data handshake control has been set

to [Enabled], the status result will not be

updated until [Result acquisition complete

notice] (Address2, Bit0 of Command Control)

is input.

“Operating procedure of the data I/O

communication” (Page 5-32)

6

Once you have finished configuring the

settings, touch the [OK] button.

Data I/O communication setting method

5