beautypg.com

Speed reference selection, Enabling the position loop, Position reference selection – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Reference Manual User Manual

Page 97

background image

Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

97

Detailed Drive Operation Chapter 1

loop can be scaled to different units other than feedback counts, for example,
degrees or inches. Typical applications for the point to point function would be
turn tables and storage retrieval machines.

Speed Reference Selection

The speed reference should be set to zero speed when using point to point
positioning. For example, set parameter 27 [Speed Ref A Sel] = 0 “Zero Speed.”

Enabling the Position Loop

The firmware function for the position loop must be turned on by setting
parameter 147 [FW Functions En], bit 16 “PositionCtrl” = 1.

To enable the position loop, set parameter 151 [Logic Command], bit 13
“PositionEnbl” = 1.

Then to allow the output of the position loop to trim the speed set parameter 740
[Position Control], bit 1 “Speed Out En” = 1.

Position Reference Selection

For point to point positioning set parameter 742 [Position Ref Sel] = 2 “Pt to Pt”.
Parameter 758 [Pt-Pt Posit Ref ] becomes the reference for the position.

Reference

Selection

(Mode)

758

Pt-Pt Posit Ref

742

Position Ref Sel

Gear Rat

[ N ]
[ D ]

+

Position

Offset

PI

Regulator

Point to

Point

768

PositReg P Gain

762

Position Fdbk

318

Position

Feedback

Selection

Proportional Channel

Posit Spd Output

0

1

749

743

742

Interp Position

Aux Posit Ref

2

758

Pt-Pt Posit Ref

Posit Ref Sel

Selected
Position
Reference