Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Reference Manual User Manual
Page 178
178
Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011
Chapter 1 Detailed Drive Operation
To control from a communication network (20-COMM module):
1.
Toggle bit 1 “Start” in the logic command word on and then off to perform
a start.
2.
Toggle bit 9 “CoastStop” in the logic command word on and then off to
perform a coast stop.
To configure the drive for 3-wire control with a current limit stop:
For parameter 153 [Control Options], set bit 8 “3WireControl” = 1.
To control from digital inputs:
1.
Set one of the parameters 825…830 [Dig In
x Sel] = 18 “CurLim Stop.”
2.
Set a second parameter 825…830 [Dig In
x Sel] = 5 “Start.”
To control from a communication network (20-COMM module):
1.
Toggle bit 1 “Start” in the logic command word on and then off to perform
a start.
2.
Toggle bit 8 “CurrLimStop” in the logic command word on and then off to
perform a current limit stop.
Note:
In 3-wire mode, all stops commanded by pressing the HIM Stop button
are ramp stops.
Configuring the Start and Stop for 2-Wire Control (Maintained
Start and Stop)
To configure the drive for 2-wire control with a ramp stop:
Set parameter 153 [Control Options] bit 8 “3WireControl” = 0.
To control from digital inputs:
• Set one of the parameters 825-…830 [Dig Inx Sel] = 7 “Run”
To control from a communication network (20-COMM module):
1.
Turn on bit 1 “Start” in the logic command word to run.
2.
Turn off bit 1 “Start” in the logic command word to perform a ramp stop.