Chapter 1 Detailed Drive Operation
Parameter 418 [Brake TP Sel] selects a value to monitor for diagnostics of the
dynamic brake protection. Parameter 419 [Brake TP Data] displays the data
selected in parameter 418 [Brake TP Sel]. Possible selections for parameter 418
[Brake TP Sel] are:
Cable, Control
Refer to the
Wiring and Grounding Guidelines for Pulse Width Modulated
(PWM) AC Drives Installation Instructions, publication
detailed information.
Cable, Lengths for Motors
Refer to the
Wiring and Grounding Guidelines for Pulse Width Modulated
(PWM) AC Drives Installation Instructions, publication
detailed information.
Cable, Power
Refer to the
Wiring and Grounding Guidelines for Pulse Width Modulated
(PWM) AC Drives Installation Instructions, publication
detailed information.
Par 418 [Brake TP Sel] Setting Description
0 - “Zero”
Do not monitor any test point for the brake protection.
1 - “Duty Cycle”
Actual duty cycle of the dynamic brake IGBT where a value of 0 in
parameter 419 [Brake TP Data] = full open and 1 = full on.
2 - “Power Actual”
Actual power applied to the resistor (Watts).
3 - “Max BodyTemp”
Maximum temperature that the resistor body can handle (°C).
4 - “Max ElemTemp Act”
Maximum temperature that the resistor element can handle (°C).
5 - “BodyTemp Act”
Predicted temperature of the resistor body (°C).
6 - “ElemTemp Act”
Predicted temperature of the resistor element (°C).
7 - “BTmpTrip Stat”
Maximum resistor body temperature has been exceeded when
parameter 419 [Brake TP Data] = 1.
8 - “ETmpTripStat”
Maximum resistor element temperature has been exceeded when
parameter 419 [Brake TP Data] = 1.
9 - “Int DB Ohms”
Rating of the internal resistor when an internal resistor is installed
(Ohms).
10 - “Data State”
A value of 0 in parameter 419 [Brake TP Data] = initial state, 1 =
internal resistor data loaded, 2 = external resistor data loaded.
11 - “MC BrakeEnbl”
A value of 0 in parameter 419 [Brake TP Data] = dynamic braking
disabled, 1 = dynamic braking enabled.
12 - “1/rdb”
Inverse of the resistance (1/Ohm).
13 - “1/th_eb”
Inverse of the thermal impedance from the resistor element to
body (Watts/°C).
14 - “1/ce”
Inverse of the resistor element thermal mass (°C/W x sec).
15 - “tamax”
Maximum ambient temperature of resistor (°C).
16 - “1/th_ba”
Inverse of the thermal impedance from the resistor body to
element (Watts/°C).
17 - “1/cb”
Inverse of the resistor body thermal mass (°C/W x sec).
18 - “DB IGBT Amp”
IGBT current rating (Amps).