Analog outputs, Analog output specifications, Analog output configuration – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Reference Manual User Manual
Page 17
![background image](/manuals/581691/17/background.png)
Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011
17
Detailed Drive Operation Chapter 1
Analog Outputs
Analog Output Specifications
There are two analog outputs, differential, configurable for +/-10V or 0…20 mA.
The D/A (digital to analog) converter is 11 bits plus the sign bit.
Analog Output Configuration
Parameters 831 and 838 [Anlg Out
x Sel] are use to specify the signal used on
Analog Outputs 1 and 2, respectively. These parameters can be programmed to
the following selections:
*Additionally, the analog output can be user configured for some other value by
setting [Anlg Out
x Sel] to 0 “User Select” and linking either parameter 832 or
839 [Anlg Out
x DInt] to a DInt (double integer) parameter or linking parameter
833 or 840 [Anlg Out
x Real] to a floating point (real) parameter.
Parameter 834 or 841 [Anlg Out
x Offset] is added to [Anlg Outx Real] or [Anlg
Out
x DInt] before the scaling and limiting blocks.
The result of [Anlg Out
x Offset] plus [Anlg Outx Real] or [Anlg Outx DInt] is
limited by 10 times the value of parameter 835 or 842 [Anlg Out
x Scale]. Then
that limited value is divided by the value of [Anlg Out
x Scale].
Parameter 836 or 843 [Anlg Out
x Zero] is added after the scaling and limiting of
the analog output value. [Anlg Out
x Zero] can be used to null out any offset from
the D/A converter.
Parameter 837 or 844 [Anlg Out
x Value] displays the voltage or current value for
the analog output.
Bit Selection
Corresponding
Parameter
Bit Selection
Corresponding
Parameter
0
“User Select”
(*see below)
15 “Motor TrqRef”
303 [Motor Torque Ref]
1
“Output Freq”
310 [Output Freq]
16 “MtrTrqCurRef”
305 [Mtr Trq Curr Ref]
2
“Sel Spd Ref”
40 [Selected Spd Ref]
17 “Speed Ref”
301 [Motor Speed Ref]
3
“Output Curr”
308 [Output Current]
18 “Speed Fdbk”
71 [Filtered SpdFdbk]
4
“Trq Cur (Iq)”
499 [Trq Cur Fdbk (Iq)]
19 “Torque Est”
471 [Estimated Torque]
5
“% Motor Flux” 309 [% Motor Flux]
20 “Scl Spd Fdbk”
72 [Scaled Spd Fdbk]
6
“Output Power” 311 [Output Power]
21 “RampedSpdRef” 43 [Ramped Spd Ref]
7
“Output Volts”
307 [Output Voltage]
22 “Spd Reg Out”
101 [SpdReg Integ Out]
8
“DC Bus Volts”
306 [DC Bus Voltage]
23 “MOP Level”
1090 [MOP Level Real]
9
“PI Reference”
181 [PI Reference]
24 “Trend 1 DInt”
572 [Trend Out1 DInt]
10
“PI Feedback”
182 [PI Feedback]
25 “Trend 1 Real”
573 [Trend Out1 Real]
11
“PI Error”
183 [PI Error]
26 “Trend 2 DInt”
576 [Trend Out2 DInt]
12
“PI Output”
180 [PI Output]
27 “Trend 2 Real”
577 [Trend Out2 Real]