Data Table

Chapter 3

3Ć22

Figure 3.7

Relationship of Word Address to Hardware

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

1

0

0

1

0

1

1

1

1

1

1

0

0

0

0

1

0

0

012

8

1

0

0

0

1

0

1

1

1

1

0

0

0

0

3ĆDigit Word Addresses

Output Module in

Assigned I/O Rack No. 1,

I/O Group No. 2

Output Terminal

012/06

010

8

Energized

Output

Input Image Table

BIT 113/12

1 = ON

0 = OFF

UserĆProgrammed Rung

Input Terminal

113/12

Input Module in

I/O Rack No. 1,

I/O Group No. 3

2-Digit Bit and

Terminal Address

Output Image Table

BIT 012/06

1 = ON

0 = OFF

012

( )

| ą|

Closed

Input

017

8

113

8

110

8

177

8

06

12

113

Instruction

Intensified

When Enabled

When the input device wired to terminal 113/12 opens, the input module
senses no voltage. The Off condition is reflected in the input image table
bit 113/12. During the program scan, the processor examines bit 113/12
for an On (1) condition. Since the bit is off (0), logic continuity is not
established, the rung is false and the output instruction is not intensified.
The processor then sets output image table bit 012/06 to off (0). In the next
I/O scan, it turns off terminal 012/06 and the output device wired to this
terminal is turned off.