Data Transfer File Instructions

Chapter 12

12Ć5

Figure 12.4

Example of an Internally Indexed File Instruction

FILE-TO-FILE MOVE

COUNTER ADDR: 214
POSITION: 001
FILE LENGTH: 014
FILE A: 512- 527
FILE R: 562- 577
RATE PER SCAN: 014

214

(EN)

17

214

(DN)

15

Notice that another term has been added to the instruction block: rate per
scan. It defines the number of words in the file operated upon during one
scan. Its value is user-chosen according to how the file operation is to take
place. There are three modes of operation based on rate per scan. They are:

Complete
Distributed complete
Incremental

The relationship between the rate per scan and the modes of operation are
summarized in Table 12.A.

Table 12.A

Modes of Instruction Operation

Mode of Operation

R = Rate Per

Scan

Number of Words Operated Upon

COMPLETE

R = File Length

Entire file per scan

DISTRIBUTED COMPLETE

0 < R < File

Length

R words per scan

INCREMENTAL

R = 0

One word per rung transition

Complete Mode

In the complete mode, the rate per scan is equal to the file length, and the
entire file is operated upon in one scan. On a false-to-true transition of the
rung condition, the instruction is enabled and the accumulated value of the
file counter is internally indexed from the first to the last word of the file.
As the accumulated value points to each word, the operation defined by the
File instruction is performed. The operation of a File instruction in the
complete mode is shown in Figure 12.5.