Data Transfer File Instructions

Chapter 12

12Ć17

Figure 12.15

FILEĆTOĆWORD MOVE Format

FILE-TO-WORD MOVE

COUNTER ADDR: 030
POSITION: 001
FILE LENGTH: 001
FILE A: 110- 110
WORD ADDRESS: 010

030

(DN)

15

Numbers shown are default values. Bold numbers must be replaced by userĆentered values. The number of default address digits

initially displayed Ċ 3, 4, or 5 Ċ will depend on the size of the data table. Initially displayed default values are governed by the I/O rack

configuration.

COUNTER ADDRESS : Address of the instruction in the accumulated value area of the data table.
POSITION : Current word being operated upon (accumulated value of counter).
FILE LENGTH : Number of words in file (preset value of the counter).
FILE A : Starting address of source file.
WORD ADDRESS : Address of destination word outside the file.

Figure 12.16 shows the format of Figure 12.15 after the conditions listed
below have been entered:

COUNTER ADDR – 200
POSITION – 005
FILE LENGTH – 010
FILE A – starts at 474 and ends at 505
WORD ADDR – 400

The procedure for using the data monitor mode to enter and/or monitor file
data is presented in Section 12.5.