Timer and Counter Instructions

Chapter 5

5Ć10

timer, the CTU instruction continues to increment its accumulated value
after the preset value has been reached. If the accumulated value goes
above 999, bit 14 is set on to indicate an overflow condition and the CTU
continues up-counting from 000. Bit 14 can be examined to cascade
counters for counts greater than 999 (Section 5.3).

Figure 5.7

UpĆCounter Diagram and Programming for Preset = 9

ON

OFF

ЙЙЙЙ

ЙЙЙЙ

1

2

3

4

5

6

7

8

9 10 11

Overflow Bit Comes On at 1000th Event. The Counter Does Not Reset.

Event to be

Counted, 111/11

AC = PR

997 998 999 1 2

0

Accumulated Value

ON

OFF

Enable Bit

053/17

ON

OFF

Count Complete

Bit 053/15

ЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙ

ЙЙЙЙ

ЙЙЙЙ

ЙЙЙЙ

ON

OFF

Output Lamp

013/06

ЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙ

ON

OFF

Overflow Bit

0137/07

ЙЙЙЙ

ЙЙЙЙ

ON

OFF

Overflow Output

013/07

Rung 1 - CTU Instruction

Preset to 9.

Rung 2 - Counter Tuns On

Bit 013/06 at Count

Complete.

|ą|

11

( CTU )

111 053

|ą|

15

(ą)

06

053 013

PR 009

AC 009

Count Switch

Count Complete Bit Output Lamp

Rung 3 - Counter Turns On

Bit 013/07 at Overflow.

|ą|

14

(ą)

053 013

Overflow Bit

07

Overflow Lamp

ЙЙЙЙ

ЙЙЙЙ