Bit Shifts

Chapter 14

14Ć4

Figure 14.2

BIT SHIFT LEFT Format

BIT SHIFT SHIFT

COUNTER ADDR: 030
NUMBER OF BITS: 001
FILE: 110- 110
INPUT: 010/00
OUTPUT: 010/00

030

(EN)

17

Numbers shown are default values. Bold numbers must be replaced by userĆentered values. The number of default address digits

initially displayed Ċ 3, 4, or 5 Ċ will depend on the size of the data table. Initially displayed default values are governed by the I/O rack

configuration.

COUNTER ADDRESS : Address of the instruction in the accumulated value area of the data table.
NUMBER OF BITS : Number of bits in the file.
FILE : Starting address of file.
INPUT : Address of input bit.
OUTPUT : Address of output bit.

030

(DN)

15

Figure 14.3 shows the format of Figure 14.2 after the following conditions
have been entered.

COUNTER ADDR – 200
NUMBER OF BITS – 128
FILE – The bit register starts and ends at word 400

8

and 407

8

respectively.
INPUT – The input bit is bit 17 of word 130

8

.

OUTPUT – The output bit is bit 00 of word 420

8

.

The procedure for using the data monitor mode for data entry on the
monitor is presented in Chapter 12. Note that bit 00 is the right side on