3 programming immediate i/o instructions – Rockwell Automation 1772-LP3 PLC - 2/30 Programmable Controller Programming and Operations Manual User Manual

Page 150

background image

Output Override and I/O Update Instructions

Chapter 7

7Ć8

The Immediate I/O instructions are programmed with the processor in
the program mode. When entered from the industrial terminal, they will
be displayed as intensified and blinking with the reverse-video cursor
positioned on the first digit of the default word address. The number of
digits in the default address can range from 4 to 5 depending on data table
size. Refer to Table 7.A for a summarized description of these instructions.

The 4- or 5-digit default word address with leading zeros will
automatically appear above the instruction provided the data table has been
expanded accordingly. To enter a 4- or 5-digit address when 4 or 5 digits
are displayed, the programmer must enter leading zeros before entering the
word address.

Table 7.A

Output Override and I/O Update Instructions

NOTE: The MCR and ZCL boundary instructions have no word address.
The word addresses, XXX, of the IMMEDIATE INPUT and OUTPUT instructions are limited to the Input and Output Image Tables respectively.
Displayed word addresses will be 3, 4, or 5 digits long, depending on Data Table size. When entering the word address, use a leading zero if

necessary.

Keytop Symbol

Instruction Name

1770ĆT3 Display

Description

-(MCR)-

MASTER CONTROL

RESET

-(MCR)-

Two MCR instructions are required to control a group of

outputs. The first MCR instruction is programmed with

input conditions to begin the zone. The second MCR

instruction is programmed unconditionally to end the zone.
When the first MCR rung is FALSE, all outputs within the

zone, except those forced ON or latched ON, will be

deĆenergized.
Do not overlap MCR zones, or nest with ZCL zones. Do

not JUMP to LABEL in MCR zones.

-(ZCL)-

ZONE CONTROL

LAST STATE

-(ZCL)-

Two ZCL instructions are required to control a group of

outputs. The first ZCL instruction is programmed with input

conditions to begin the zone. The second ZCL instruction

is programmed unconditionally to end the zone.
When the first ZCL rung is FALSE, outputs in the zone will

remain in their last state.
Do not overlap ZCL zones, or nest with MCR zones. Do

not JUMP to LABEL in ZCL zones.

-[ I ]-

IMMEDIATE INPUT

ĂXXX

-[ I ]-

Processor interrupts program scan to update Input Image

Table with data from the corresponding Module group. It is

updated before the normal I/O scan and executed each

program scan.

-(IOT)-

IMMEDIATE OUTPUT

ąXXX

-(IOT)-

When the rung is TRUE, Processor interrupts program

scan to update Module group with data from corresponding

Output Image Table word address. It is updated before the

normal I/O scan and executed each program scan when

the rung is TRUE. Can be programmed unconditionally.

7.3
Programming Immediate I/O
Instructions