Block Transfer

Chapter 10

10Ć10

Figure 10.5

Programming Multiple Reads from One Module

BLOCK TRANSFER READ

DATA ADDR

052

MODULE ADDR

141

BLOCK LENGTH

04

FILE

160Ćă167

014

(EN)

17

114

(DN)

17

1

|ą|

BLOCK TRANSFER READ

DATA ADDR

052

MODULE ADDR

141

BLOCK LENGTH

08

FILE

160Ćă167

014

(EN)

17

114

(DN)

17

BLOCK TRANSFER READ

DATA ADDR

052

MODULE ADDR

141

BLOCK LENGTH

03

FILE

160Ćă167

014

(EN)

17

114

(DN)

17

014

(ą)

17

|ą|

2

| / |

3

| / |

1

| / |

2

|ą|

3

| / |

1

| / |

2

| / |

3

|ą|

|ą|

|ą|

Inputs

Inputs

Inputs

Input 1

Input 2

Input 3

NOTES:

1.

The same discussion applies when programming multiple writes of
different block lengths to one module.

2.

Up to 50 read or write block transfers is the maximum amount that
can be handled by Rev J firmware of the 1772-LG processor module.