Addressing

Appendix A

AĆ6

Using 16ĆPoint I/O Modules

High-Density (16-point) I/O modules provide 16 input terminals or 16
output terminals. 16-point I/O modules use a full word in the input or
output image table. Two 16-point modules (one input and one output) can
be used in a 2-slot I/O group (Figure A.4).

Figure A.4

Illustration of 2Ćslot Addressing with 16Ćpoint Input and Output Modules

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

Input
Terminals

Output
Terminals

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

Output image table word corresponding

to the I/O group (all bits used).

Input image table word corresponding

to the I/O group (all bits used).

2Ćslot

I/O Group

NOTE: 16Ćpoint input and output

modules use two words (one input,

one output) of the image table.

Because these modules use a full word in the image table, the only type of
module you can use in a 2-slot I/O group with a 16-point module is one