Configuring the I/O
4-31
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
SLC 500 Controller Example
After the adapter is configured, the connected drive and adapter will be a
single node on the network. This section provides the steps needed to
configure a simple EtherNet/IP network (see
). In our example,
we will configure a SLC 500 controller to communicate with a drive using
Logic Command/Status, Reference/Feedback, and Datalinks over the
network.
Figure 4.12 Example SLC 500 Controller EtherNet/IP Network
Configuring Parameters for Network I/O
Because the I/O for the drive is message-based, there is no need to configure
any I/O inside the RSLogix 500 project, version 7.00 or later, until using the
I/O as described in
However, to get the adapter to operate with the I/O created in
need to configure the adapter to accept the I/O and drive to point to the
appropriate Datalinks.
1. Set adapter Parameters 23 - [DPI I/O Cfg], 35 - [M-S Input], and 36 -
[M-S Output] to values that meet your application requirements.
For this example, the adapter I/O parameters are set to these values.
2. Reset the adapter (see
Resetting the Adapter on page 3-16
) or power
cycle the drive.
For the drive speed reference and Datalink parameter values and the
adapter setup parameter values, see
IP Address 10.91.100.80
SLC 500 Controller with Embedded Ethernet
IP Address 10.91.100.79
PowerFlex 70 Drive with
20-COMM-E Adapter
Computer with
Ethernet Connection
Ethernet
Switch
TIP: Information for PowerFlex 750-Series drives has been added to this
manual where it is applicable.
Adapter Parameter No.
Setting
23 - [DPI I/O Cfg]
xxxx xxxx xxx1 1111
35 - [M-S Input]
xxxx xxxx xxx1 1111
36 - [M-S Output]
xxxx xxxx xxx1 1111