Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual
Page 228
![background image](/manuals/577124/228/background.png)
B-2
Adapter Parameters
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
12
13
14
15
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
Sets the gateway address bytes for the adapter’s
gateway address when
Parameter 03 - [BOOTP]
is set to ‘0’ (Disabled).
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
255
Type:
Read/Write
Reset Required: Yes
16
[EN Rate Cfg]
Sets the speed and duplex network data rate at
which the adapter communicates. (Updates
Parameter 17 - [EN Rate Act] after a reset.)
Default:
0 = Autodetect
Values:
0 = Autodetect
1 = 10 Mbps Full
2 = 10 Mbps Half
3 = 100 Mbps Full
4 = 100 Mbps Half
Type:
Read/Write
Reset Required: Yes
17
[EN Rate Act]
Displays the actual speed and duplex network data
rate used by the adapter.
Values:
0 = No Link
1 = 10 Mbps Full
2 = 10 Mbps Half
3 = 100 Mbps Full
4 = 100 Mbps Half
Type:
Read Only
18
[Ref/Fdbk Size]
Displays the size of the Reference/Feedback. The
drive determines the size of the Reference/
Feedback.
Values:
0 = 16-bit
1 = 32-bit
Type:
Read Only
19
[Datalink Size]
Displays the size of each Datalink word. The drive
determines the size of Datalinks.
Values:
0 = 16-bit
1 = 32-bit
Type:
Read Only
20
[Reset Module]
No action if set to ‘0’ (Ready). Resets the adapter if
set to ‘1’ (Reset Module). Restores the adapter to
its factory default settings if set to ‘2’ (Set Defaults).
This parameter is a command. It will be reset to ‘0’
(Ready) after the command has been performed.
Default:
0 = Ready
Values:
0 = Ready
1 = Reset Module
2 = Set Defaults
Type:
Read/Write
Reset Required: No
Parameter
No. Name and Description
Details
255.255.255.255
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
!
ATTENTION: Risk of injury or equipment damage exists. If the adapter is
transmitting I/O that controls the drive, the drive may fault when you reset the
adapter. Determine how your drive will respond before resetting a connected
adapter.